| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/17/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*PROVIDE DUCT EXTENSION ON TYPE I COOKING HOOD VENT BLOWER. DIRECT AWAY FROM ROOF TOP COMB. A/C UNIT ADJOINING BLOWER. TERMINATE ABOVE TOP OF UNIT. |
|
| 10/29/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*NO INSPECTION HAVE EVER BEEN CALLED FOR MECHANICAL REMOVE CEILING TILES KITCHEN REMOVE INSULATION LAYING ON TOP OF HOOD. REMOVE DUCT WRAP FROM GREASE DUCT EXPOSE WATER HEATER VENT. PROVIDE EQUIPMENT SCHEDULE NOT SHOWN ON PLANS. RAISE SEWER VENTS 2' ABOVE ANY AIR INTAKE INTO BLDG. PROVIDE A ROOF JACK ON WATER HEATER VENT PROVIDE AN OUTSIDE AIR VENT CONDENSATE CANNOT BE DRILLED IN THE SIDE OF A WASTE VENT WHERE IS EXHAUST & SUPPLY FOR LAUNDRY ROOM ? PROVIDE COMBUSTION AIR VENTS. |