Permit: T00CM02201

Parcel: 10709023A


Addresses:

2537 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
01/21/2003 ELECTRIC - UNDERGROUND Approved
12/07/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
12/04/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*250 MCM RHH/RHW IS INSTALLED W/#6 RHH/RHW PLANE CALL FOR 3/0 & #6 IN 2" CONDUIT. PLEASE REVISE PLANS OR INSTALL AS PER PLAN HAVE CITY APPROVE REUSSION ALSO NEED SPEC SHEET TO VERIFY IF ALUM. WIRE IS ALLOWED.