Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2003 | ELECTRIC - FINAL | Approved | OWNER & CONTRACTOR TO PROVIDE ENCLOSURE FOR CLOSET LTS. AND LAST SHIELD REMAINING. | |
| 12/30/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) WHERE IS DISCONNECTING MEANS FOR WATER HEATER? UNIT "A" 2.) PROTECT BULB ON CLOSETS LIGHT 3.) PANELS/DISCONNECTING MEANS FOR WATER HEATER TO HAVE WORKING SPACE & CLEARENCE PER 110-26 UNIT"B" 4.) FILL UNUSED OPENING IN PANEL "B" 5.) USE AN ANTIOXIDE COMPOUND WITH ALUMINUM CONDUCTORS PANEL "B" 6.) MISSING A COVER PLATE IN CLOSET. 7.) TIGHTEN LOOSE FITTINGS AT A/C UNITS. 8.) OUTDOOR LIGHT TO MEET TUCSON LIGHTING CODE SECTION #5. 9.) FINISH ITEM #1,3,4,6 &8 OF PREVIOUS INSPECTION. |
|
| 10/29/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) LABEL PANEL ON OUTSIDE COVER 2.) WE HAVE EXPOSED CONDUCTORS PASSING THROUGH COMBUSTABLE MATERIAL ALSO SECURE TO PANEL. 3.) INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANFACTURES REQUIREMENTS. 4.) BONDING DEVICES NEED ON BOTH SIDES OF SERVICE NIPPLES 5.) PROVIDE "R" PINS FOR FUSES. 6.) SUPPORT CONDUIT FOR IRRIGATION CONTROLER 7.) VERIFY LISTING LABELS FOR KITCHEN EQUIIPMENT. 8.) AN EXTENDER RING IS NEEDED WHERE MORE THAN 1/8" BETWEEN THE BOX AND DEVICE OR FIXTURES. 9.) CONNECT ALL GROUND WIRES. 10.) BATHROOM RECEPTACLE TO BE GFCI PROTECTED. 11.) ALL KITHCEN RECEPTACLE SERVING COUNTER TOPS TO BE GFCI PROTECTED. 12.) WHERE IS OUTLET ALONG WALL SPACE AT KITCHEN WALL. | |
| 11/26/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*MEET WITH CONTRACTOR GREEN LEE TO DISCUSS. PROJECT. |