Case Number: T05FR00823
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 24
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/07/2005 VIOL - ADMINISTRATION JLANGEJA Violation TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy.
06/07/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.2.1- A sign shall be permanently displayed near each fire door in letters not less than 1" to read as follows: "FIRE DOOR-DO NOT BLOCK"
06/07/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.4- Fire doors shall be inspected and tested annually to confirm proper operation and full closure. A written record shall be maintained and available. (loading dock/warehouse)
06/08/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Violation TFC 510.1- Fire protection equipment shall be identified in an approved manner. Sprinkler riser room shall have a sign stating "AUTOMATIC SPRINKLERS" in a conspicuous location.
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space shall be provided by the outside electrical equipment (S wall)
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space...electrical. (vending room)
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters are prohibited. (vending room)
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall be prohibited. 1. W wall in locker room 2. sales office 3. N wall of N offices
06/08/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Violation TFC 2604.1.5- Partitions separating hot works area from other areas of the building shall be non-combustible and securely attached to the floor. (maint. shop)
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.1.1(1)- Maximum allowable quantity per control area of Class 1-B flammable liquids 120 gallons.
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.1.1(2)- Maximum allowable quantity of toxic gas per control area shall not exceed 810 cubic feet. *** 1-150 lb bottle = 771 cubic feet ***
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. (helium tank in storage rack marked acetylene, maint. facility)
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation TFC 2703.8.3.2- Maximumnumber of control areas is 4 on the ground level.
06/08/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured. (5 + 1 acetylene)
06/08/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured. (chlorine)
06/08/2005 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3403.1.3- Class 1 electrical equipment is required within 10 feet of solvent tanks.
06/08/2005 VIOL - TOXIC MATERIALS JLANGEJA Violation TFC 3704.1.2- Gas cabinets containing toxic compressed gases shall comply with the following requirements: 1. The average ventilation velocity at the face of the gas cabinet access port or window shall not be less than 200 fpm with a minimum of 150 fpm at any point of the access port or window. 2. Gas cabinets shall be connected to an exhaust system. 3. Gas cabinets shall not be used as the sole means of exhaust for any room or area. 4. The maximum number of cylinders located in a single gas cabinet shall not exceed 3. 5. Gas cabinets shall be equipped with an approved automatic sprinkler system.
06/08/2005 VIOL - TOXIC MATERIALS JLANGEJA Violation TFC 3704.2.2.1- Cylinders shall be located within gas cabinets, exhausted enclosures or gas rooms.
06/09/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage of combustibles shall be 18" below sprinklers. (vending room)
06/09/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be inspected annually. Not required, can be removed. (vending room)
06/09/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 903.3.3- Automatic sprinklers shall be installed in and under areas that exceed 4 feet. (vending parts room)
06/09/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- Path of egress shall be unobstructed. 1. pallets stacked on stairway to cap room 2. bollard in path outside W door
06/09/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1009.11- Stairways shall have handrails on both sides. (vending room)

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00823
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/21/2007 INSP - REINSPECTION JLANGEJA Approved Met with Darrel to see where generator was to be set. Concrete pad will be poured in the next week, needs 2 weeks to cure. Generator to be set afterwards. Introduced MA85 as new contact person.