Case: T05FR00823
Case Details
Entered Date:
06/07/2005
Applicant:
N/A
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00823
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 24
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 06/07/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. |
| 06/07/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.2.1- A sign shall be permanently displayed near each fire door in letters not less than 1" to read as follows: "FIRE DOOR-DO NOT BLOCK" |
| 06/07/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.4- Fire doors shall be inspected and tested annually to confirm proper operation and full closure. A written record shall be maintained and available. (loading dock/warehouse) |
| 06/08/2005 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | TFC 510.1- Fire protection equipment shall be identified in an approved manner. Sprinkler riser room shall have a sign stating "AUTOMATIC SPRINKLERS" in a conspicuous location. |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space shall be provided by the outside electrical equipment (S wall) |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space...electrical. (vending room) |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters are prohibited. (vending room) |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall be prohibited. 1. W wall in locker room 2. sales office 3. N wall of N offices |
| 06/08/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2604.1.5- Partitions separating hot works area from other areas of the building shall be non-combustible and securely attached to the floor. (maint. shop) |
| 06/08/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.1.1(1)- Maximum allowable quantity per control area of Class 1-B flammable liquids 120 gallons. |
| 06/08/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.1.1(2)- Maximum allowable quantity of toxic gas per control area shall not exceed 810 cubic feet. *** 1-150 lb bottle = 771 cubic feet *** |
| 06/08/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. (helium tank in storage rack marked acetylene, maint. facility) |
| 06/08/2005 | VIOL - HAZARDOUS MATERIALS,GEN | JLANGEJA | Violation | TFC 2703.8.3.2- Maximumnumber of control areas is 4 on the ground level. |
| 06/08/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured. (5 + 1 acetylene) |
| 06/08/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured. (chlorine) |
| 06/08/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3403.1.3- Class 1 electrical equipment is required within 10 feet of solvent tanks. |
| 06/08/2005 | VIOL - TOXIC MATERIALS | JLANGEJA | Violation | TFC 3704.1.2- Gas cabinets containing toxic compressed gases shall comply with the following requirements: 1. The average ventilation velocity at the face of the gas cabinet access port or window shall not be less than 200 fpm with a minimum of 150 fpm at any point of the access port or window. 2. Gas cabinets shall be connected to an exhaust system. 3. Gas cabinets shall not be used as the sole means of exhaust for any room or area. 4. The maximum number of cylinders located in a single gas cabinet shall not exceed 3. 5. Gas cabinets shall be equipped with an approved automatic sprinkler system. |
| 06/08/2005 | VIOL - TOXIC MATERIALS | JLANGEJA | Violation | TFC 3704.2.2.1- Cylinders shall be located within gas cabinets, exhausted enclosures or gas rooms. |
| 06/09/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be 18" below sprinklers. (vending room) |
| 06/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be inspected annually. Not required, can be removed. (vending room) |
| 06/09/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 903.3.3- Automatic sprinklers shall be installed in and under areas that exceed 4 feet. (vending parts room) |
| 06/09/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- Path of egress shall be unobstructed. 1. pallets stacked on stairway to cap room 2. bollard in path outside W door |
| 06/09/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1009.11- Stairways shall have handrails on both sides. (vending room) |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00823
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2007 | INSP - REINSPECTION | JLANGEJA | Approved | Met with Darrel to see where generator was to be set. Concrete pad will be poured in the next week, needs 2 weeks to cure. Generator to be set afterwards. Introduced MA85 as new contact person. |