Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space shall be provided by the outside electrical equipment (S wall) | |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall be prohibited. 1. W wall in locker room 2. sales office 3. N wall of N offices |
|
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space...electrical. (vending room) | |
| 06/08/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters are prohibited. (vending room) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (N wall) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5- Extension cord on bottling rack. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3.1- Disconnecting means for boiler shall be clearly marked. Remove sign from breaker panel inside. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Electrical hazards shall be abated. There are frayed, exposed wires in hot works area. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords are prohibited. (hot works area) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3- A working space of 30 x 36 x 78 shall be provided in front of electrical service equipment. (ammonia gas room) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 606.7- Refrigeration system shall be provided with approved emergency signs in accordance with NFPA 704. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 606.9.1- A clearly identified switch of the break-glass type shall provide off-only control of electrically energized equipment and appliances in the machinery room, other than refrigerant leak detectors and machinery room ventilation. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 606.9.2- A clearly identified switch of the break-glass type shall provide on-only control of the machinery ventilation fans. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 604.2.10- Emergency power shall be provided for occupancies with toxic materials in accordance with 3704.2.2.8. | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Open wiring splices, open junction boxes and extension cords shall be prohibited. (outside gas room) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Blanks shall be provided in openings inside electrical panel. (W wall) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Piggy-backing of surge protectors shall be prohibited. (service techs by drill press) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space for electrical equipment. (W wall) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space in front of electrical panels. (battery station) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall be prohibited. (through fire door) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Non-functional extension cords attached to wall shall be removed. (warehouse) | |
| 06/07/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. (door alarm,E) |