Case: T05FR00823

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space shall be provided by the outside electrical equipment (S wall)
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall be prohibited.
1. W wall in locker room
2. sales office
3. N wall of N offices
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space...electrical. (vending room)
06/08/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters are prohibited. (vending room)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (N wall)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5- Extension cord on bottling rack.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3.1- Disconnecting means for boiler shall be clearly marked. Remove sign from breaker panel inside.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Electrical hazards shall be abated. There are frayed, exposed wires in hot works area.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords are prohibited. (hot works area)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3- A working space of 30 x 36 x 78 shall be provided in front of electrical service equipment. (ammonia gas room)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 606.7- Refrigeration system shall be provided with approved emergency signs in accordance with NFPA 704.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 606.9.1- A clearly identified switch of the break-glass type shall provide off-only control of electrically energized equipment and appliances in the machinery room, other than refrigerant leak detectors and machinery room ventilation.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 606.9.2- A clearly identified switch of the break-glass type shall provide on-only control of the machinery ventilation fans.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 604.2.10- Emergency power shall be provided for occupancies with toxic materials in accordance with 3704.2.2.8.
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Open wiring splices, open junction boxes and extension cords shall be prohibited. (outside gas room)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Blanks shall be provided in openings inside electrical panel. (W wall)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Piggy-backing of surge protectors shall be prohibited. (service techs by drill press)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space for electrical equipment. (W wall)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space in front of electrical panels. (battery station)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall be prohibited. (through fire door)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Non-functional extension cords attached to wall shall be removed. (warehouse)
06/07/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes shall be prohibited. (door alarm,E)