Case: T05FR00823

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Violation

Inspection History: VIOL - TOXIC MATERIALS

Date Description Inspector Results Comments
06/08/2005 VIOL - TOXIC MATERIALS Violation TFC 3704.1.2- Gas cabinets containing toxic compressed gases shall comply with the following requirements:
1. The average ventilation velocity at the face of the gas cabinet access port or window shall not be less than 200 fpm with a minimum of 150 fpm at any point of the access port or window.
2. Gas cabinets shall be connected to an exhaust system.
3. Gas cabinets shall not be used as the sole means of exhaust for any room or area.
4. The maximum number of cylinders located in a single gas cabinet shall not exceed 3.
5. Gas cabinets shall be equipped with an approved automatic sprinkler system.
06/08/2005 VIOL - TOXIC MATERIALS Violation TFC 3704.2.2.1- Cylinders shall be located within gas cabinets, exhausted enclosures or gas rooms.