Case: T05FR00823

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
06/09/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6- Fire extinguishers shall be inspected annually. Not required, can be removed. (vending room)
06/09/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.3.3- Automatic sprinklers shall be installed in and under areas that exceed 4 feet. (vending parts room)
06/08/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.4- A building, where protected by automatic sprinklers, shall be provided with sprinklers in all areas. (cooler)
06/08/2005 VIOL - FIRE PROTECTION SYSTEMS Violation Tfc 906.7- Fire extinguishers shall be mounted on hangers or brackets.
06/08/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 912.3- Immediate access to FDCs sahll be maintained at all times without obstruction by fences.
06/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.3.3- Automatic sprinklers shall be installed in and under equipment that exceeds 4 feet. (under deck)
06/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6- Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times and shall be replaced or repaired where defective.
1. S/S shall be serviced annually
2. Fire extinguishers shall be serviced annually
3. Halon system is due for annual service in June
06/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.4- Fire extinguishing systems shall be maintained in accordance with the original installation standards for that system. The stock of spare sprinklers shall be as follows: greater than 300 heads = minimum 6 spare heads.
06/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6- The standpipe and hose system shall be inspected, tested and maintained in an operative condition at all times.
06/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.4- per NFPA 13: Where an FDC services only a portion of the building, a sign shall be attached indicating the portions of the building served. A sign indicating the riser number shall correspond with the floor plan map.