Inspection Status: Violation
Inspection History: VIOL - WELDING & OTHER HOT WRK
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2005 |
VIOL - WELDING & OTHER HOT WRK |
|
Violation |
TFC 2604.1.5- Partitions separating hot works area from other areas of the building shall be non-combustible and securely attached to the floor. (maint. shop) |
| 06/07/2005 |
VIOL - WELDING & OTHER HOT WRK |
|
Violation |
TFC 2604.1.1- Hot works areas shall not contain combustibles. Foam on walls shall be removed or covered with a non-combustible material. |
| 06/07/2005 |
VIOL - WELDING & OTHER HOT WRK |
|
Violation |
TFC 2606.4- The emergency disconnect shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment. |