Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T05FR00823

Parcel: 12418162D


Addresses:

931 S HIGHLAND AV

Inspection Status: Violation

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation TFC 2703.1.1(2)- Maximum allowable quantity of toxic gas per control area shall not exceed 810 cubic feet.
*** 1-150 lb bottle = 771 cubic feet ***
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation TFC 2703.1.1(1)- Maximum allowable quantity per control area of Class 1-B flammable liquids 120 gallons.
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation TFC 2703.8.3.2- Maximumnumber of control areas is 4 on the ground level.
06/08/2005 VIOL - HAZARDOUS MATERIALS,GEN Violation TFC 2703.5.1- Individual containers shall be conspicuously marked or labeled in an approved manner. (helium tank in storage rack marked acetylene, maint. facility)