Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Complete
Type:
Residential Building - One or Two Family
Address NEW:
1028 W COLUMBIA ST
Apply Date:
12/14/2022
Applicant:
Luis Benitez
Description:
REV1: Removed bathroom door Single Family Dwelling

Permit Reviews

Permit Number - TC-RES-1222-01528
Permit Status: Complete
Permit Description: REV1: Removed bathroom door Single Family Dwelling
Start Date Submittal Complete Date Status  
03/19/2026 RESIDENTIAL NEW DWELLING REVISION v.1 04/03/2026 APPROVED Review Details
12/13/2023 RESIDENTIAL NEW DWELLING v.1 01/02/2024 APPROVED Review Details
04/26/2023 RESIDENTIAL NEW DWELLING v.2 05/18/2023 APPROVED Review Details
02/08/2023 RESIDENTIAL NEW DWELLING v.1 03/02/2023 REQUIRES RESUBMIT Review Details
09/22/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 09/22/2026 APPROVED Review Details

Conditions

Permit Number - TC-RES-1222-01528
Permit Status: Complete
Permit Description: REV1: Removed bathroom door Single Family Dwelling
Date Description Comments
01/02/2024 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as a contact. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.
05/17/2023 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
02/28/2023 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Complete
Permit Number: TC-RES-1222-01528
Permite Description: REV1: Removed bathroom door Single Family Dwelling
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
11/13/2024 BULD - Electrical Clearance N/A Not Ready 11/13/24 not ready. box is empty. no temporary power.
01/16/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. N/A Re-inspection required 1/16/25: HVAC registers require blocks on 3 sides, DWV Must be under test, nail plates required throughout at top plates and bottom plates and in wall(plumbing,electrical, mechanical) anything within 1 1/4" of face of stud, seal all penetrations through top plates and vapor barrier throughout, pex must have a 12" clearance from can lights, pressure relief for water heater discharge not roughed in, 18" of copper required before first solder joint at pex, water lines not under pressure. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
02/18/2026 COT - RSME - Mechanical Final N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers
02/18/2026 COT - RSEL - Electrical Underground N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers
02/18/2026 COT - RSEL - Electrical Final N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers
02/18/2026 COT - RSEL - Outdoor Lighting N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers
02/18/2026 RSBU - Building Final N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers
02/18/2026 COT - RSPL - Plumbing Final N/A Re-inspection required 2.18.26
Water hammer arrestor required at dishwasher hot line
Outdoor lighting not installed
Exposed whip for garage door box
Revision required for removal of glass door in master bathroom
WR (weather resistant) receptacles required at outdoor areas
Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers

Completed Inspections

Permit Status: Complete
Permit Number: TC-RES-1222-01528
Permit Description: REV1: Removed bathroom door Single Family Dwelling
Total Completed Inspections - 18
Date Description Inspector Results Comments
02/20/2024 COT - RSPL - Rough Soil Passed
02/21/2024 COT - RSBU - Preslab Passed 2/21/24: reinforcement per plans ok to pour.
02/21/2024 COT - RSBU - Excavation/Rebar/Zoning Passed 2/21/24: reinforcement per plans ok to pour.
06/12/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed
06/12/2024 COT - RSBU - Roof Nailing Passed
07/09/2024 COT - RSPL - Yard Water Line Passed Okay to backfill. Shading required. 7/9/2024
11/15/2024 BULD - Electrical Clearance Passed 11/15/24 clearance for TEP ECO
01/22/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 1/22/25 corrections made, no further issues found
02/11/2025 COT - RSBU - Interior Shear Bracing Passed 2/11/25 pass
02/18/2026 COT - RSEL - Grounding/Bonding Passed
02/18/2026 COT - RSPL - Sewer Passed
05/19/2026 COT - RSME - Mechanical Final Passed 5-19-26: approved.
05/19/2026 COT - RSEL - Electrical Underground Passed 5-19-26: approved.
05/19/2026 COT - RSEL - Electrical Final Passed 5-19-26: electrical final approved.
05/19/2026 COT - RSEL - Outdoor Lighting Passed 5-19-26: approved.
05/28/2026 RSBU - Building Final Passed 5-28-26: building final approved.
05/28/2026 COT - RSPL - Plumbing Final Passed 5-28-26: plumbing final approved.
05/28/2026 ENGR Engineering Final Passed

Documents

File Name Document Type  
COFO_FINALCOFO_RESIDENTIAL (SSRS).PDF DOCUMENTS VIEW
BENITEZ-LAYOUT_V1.PDF DOCUMENTS VIEW
R82213174.240590_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
1370-DESCRIPTION-OF-REVISIONS2_V1.PDF DOCUMENTS VIEW
CONS-1370-DRAWINGS-REV2_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
1370-REVISION-DESCRIPTION_V1.PDF DOCUMENTS VIEW
1370REV-MANUALJ_V1.PDF DOCUMENTS VIEW
1370-REV-STRUCT-CALCS_V1.PDF DOCUMENTS VIEW
CONS-1370REV-DRAWINGS_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
1370-OWNER-BUILDER-WAIVER_V1.PDF DOCUMENTS VIEW
CONS-1370-DRAWINGS-REV_V2.PDF DOCUMENTS VIEW