Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2026 | RSBU - Building Final | Re-inspection required | 2.18.26 Water hammer arrestor required at dishwasher hot line Outdoor lighting not installed Exposed whip for garage door box Revision required for removal of glass door in master bathroom WR (weather resistant) receptacles required at outdoor areas Any and all circuits serving interior livable outlets and receptacles must be under AFCI protected breakers |
|
| 05/19/2026 | RSBU - Building Final | Re-inspection required | 5-19-26: Exposed whip for garage door, missing hammer arrestor at dishwasher, install water heater pan, wrap hose bib with R3 insulation, and install house number to structure-see plans for location. | |
| 05/28/2026 | RSBU - Building Final | Passed | 5-28-26: building final approved. |