Permit Number: TC-RES-1222-01528
Parcel: 12003041B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1222-01528
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2023 Site Engineering NOT REQUIRED
02/28/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/28/2023 Residential Building REQUIRES RESUBMIT TC-RES-1222-01528
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS :

1. All SFR and Duplex plans submitted after March 1, 2009, require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½”control conduit and two ¾” copper piping for water with rooftop termination; straight 3” capped sleeve; or an accessible attic (clear path 30” wide x 30” high) over the water heater. Show appropriate notation.
2. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3. Model plans should show four typical south facing roof surfaces.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Breaker space is at the last panel space.
3. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space or show the distance from transit or a bike boulevard as not greater than a quarter-mile.

SITE PLAN:

1. Update the electric and water lines from meter to building, R106.1.1. Show all utility point of connections without dependance on another dwelling. TEP may require the service panel for the property at the closest building to the service transformer with an underground feeder from a dual meter to the more distant dwelling.
2. Show a street address for each dwelling on the site plan, R319.
3. Show the square footage of living space, garage and covered patios, R106.1.1.
4. Sewer lines passing through an easement require an agreement statement with a Pima County recorded document number, R106.1.1.

PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806. Remove the functioning attic vents from sheet A3 and calcs sheet A5 or relocate roof insulation to the ceiling sheet A4.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A two or three bedroom dwelling of 1501 – 3000 SF requires a 60 CFM continuous setting. Update note #20.

ELECTRICAL PLANS:

1. Approval of a new Overhead service requires field verification. If used, an Underground Service Waiver request must be included with the permit application along with TEP verification.
2. Provide the Electric Vehicle Supply Equipment 40 ampere 240 volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
02/17/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-RES-1222-01528
1028 W Columbia St – R-1
New single-family dwelling (1st Review)

TRANSMITTAL DATE: February 17, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in the R-1 zone, subject to use-specific standards 4.9.7.B.5-.9.

1. Correct the dimension to 25 feet between the centerline of Columbia Street and the front street property line. Show that the distance between the face of the curb and the front street property line is 8 feet.

2. Review UDC Section 6.4.3.C and correct the lot coverage calculations. Remove the proposed walkway, porch, and terrace from the lot coverage calculations.

3. A separate permit under permit type “Residential Fence/Wall Permit” will be required for the proposed block wall and wrought iron gate.

4. A separate right-of-way permit will be required for the installation of a second curb cut. Contact the Department of Transportation and Mobility for further information.

5. Provide elevations that show the distances from design grade (the ground) to the highest point of the building wall to confirm setback requirements. Per UDC 6.4.5.C.1.a, within established areas, the required front street setback is 20 feet or one and one-half the height of the proposed building wall, whichever is greater, measured from the street property line. Per UDC Table 6.3-2.A, when a residential use is adjacent to a residential zone, the required side and rear yard setbacks are six feet or 2/3 the height of the proposed wall, whichever is greater.

If you have any questions about this transmittal, contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/08/2023 NPPO REVIEW COMPLETED
02/08/2023 PDSD Application Completeness Express REVIEW COMPLETED
02/08/2023 Site Landscape REVIEW COMPLETED