Permit: TC-MDP-0825-00458
Permit Details
Status:
Inspections
Type:
Model Building Permit
Address:
7422 S PYRAMID RIDGE DR
Address NEW:
7422 S PYRAMID RIDGE DR
Apply Date:
08/29/2025
Applicant:
Celina Rodriguez
Description:
Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
Permit Reviews
Permit Number - TC-MDP-0825-00458
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/11/2025 | SITE FROM MODEL PERMIT - PRODUCTION v.3 | 09/15/2025 | APPROVED |
| 09/02/2025 | SITE FROM MODEL PERMIT - PRODUCTION v.1 | 09/10/2025 | REQUIRES RESUBMIT |
| 09/10/2025 | SITE FROM MODEL PERMIT - PRODUCTION v.2 | 09/10/2025 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-MDP-0825-00458
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
Total Outstanding Activity Conditions - 5
| Date | Name |
|---|---|
| 08/20/2025 | Submit the Air Leakage & Duct Tightness Test Report completed by an Approved Special Inspector prior to Final Inspections. |
| 08/20/2025 | Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy. For More Information visit https://www.pima.gov/1076/Sewer-Connection-Permits, To check your permit status https://permits.pima.gov/ |
| 09/03/2025 | Post-Installed Anchor Inspection Report is required. |
| 09/03/2025 | Post-Tension Inspection Report is required. |
| 09/03/2025 | SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED. |
Conditions
Permit Number - TC-MDP-0825-00458
Permit Status: Inspections
Permit Description: Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
| Date | Description | Comments |
|---|---|---|
| 08/20/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. | |
| 08/20/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0825-00458
Permite Description: Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
Total Outstanding Inspections - 7
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2025 | COT - RSPL - Sewer | N/A | Not Ready | |
| 10/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Not Ready | 10.1.25 Work being conducted on site, trip hazards and other hazards prevalent along with visual obstruction. Site not suitable for inspection. Reinspection requires fee. |
| 09/30/2025 | COT - RSBU - Roof Nailing | N/A | Re-inspection required | 9/30/25: fasteners at shear walls shall penetrate no more than 1/8", fasteners at shear wall 11 shall be spaced at 4" at edge and 12" at field, Anchor bolts at shear wall 11 are required at 23" o.c, anchor bolt spacing at exterior walls is 72" o.c (span greater than 72" on north wall), anchor bolts shall be placed no closer than 7X the bolt diameter from edge of sill plate, 2x6 Ledge at back patio must be fastened with 4 16d nails at 16" o.c, 2x6 rafters at back patio must be spaced at 16" o.c,RSP4 spacing should be 32" o.c (missed on south wall, improperly installed MASA clip at north wall midway, 7 fasteners minimum at masa clip to suffice for 1/2" anchor bolts, shot pins must be spaced at 36" o.c at interior non-load bearing walls. Roof sheathing at garage must be properly fastened, anchor bolts must be in middle third of plate. |
| 11/17/2025 | RSBU - Building Final | N/A | Partial Pass | Okay for level 3 TCO for use as a sales model. |
| 11/17/2025 | ENGR Engineering Final | N/A | Partial Pass | Okay for level 3 TCO for use as a sales model. |
| 11/17/2025 | COT - RSPL - Plumbing Final | N/A | Not Ready | |
| 11/17/2025 | COT - RSME - Mechanical Final | N/A | Not Ready |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-MDP-0825-00458
Permit Description: Mirador Ridge Blossom 1465 Plan (Model master plan TC-MDP-0725-00408)
Total Completed Inspections - 13
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2025 | COT - RSPL - Rough Soil | Passed | ||
| 09/19/2025 | COT - RSPL - Yard Water Line | Passed | ||
| 09/23/2025 | COT - RSBU - Excavation/Rebar/Zoning | Passed | ||
| 09/23/2025 | COT - RSBU - Preslab | Passed | ||
| 09/23/2025 | COT - RSEL - Electrical Underground | Passed | ||
| 09/23/2025 | COT - RSEL - Grounding/Bonding | Passed | ||
| 10/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 10/03/2025 | COT - RSBU - Roof Nailing | Passed | ||
| 10/08/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 10-8-25: intermediates approved-okay to continue with construction. | |
| 10/08/2025 | COT - RSPL - Gas Pressure Test | Passed | 10-8-25: gas pressure test approved. | |
| 10/13/2025 | COT - RSBU - Interior Shear Bracing | Passed | ||
| 11/17/2025 | COT - RSEL - Outdoor Lighting | Passed | ||
| 12/01/2025 | BULD - Electrical Clearance | Passed | 12.1.25 approved for ECO |