Inspection Status: Not Ready

Inspection History: ENGR Engineering Final

Permit Number - TC-MDP-0825-00458

Inspection Description - ENGR Engineering Final

Inspection Status - Not Ready

Date Description Inspector Results Comments
01/20/2026 ENGR Engineering Final Not Ready Ramp with landing required for use as a model. sales fencing prevents accessible route via garage.
02/12/2026 ENGR Engineering Final Not Ready 2/12/26
TCO level 3 for display purposes only could be issued to this permit when there is an accessible route from the adjacent Commercial Office 7428 to the south. Accessible Routes are to be built from acceptable material with running slope that cannot exceed 5%. Cross slope cannot exceed 2%. If Ramps are used they cannot exceed 8.33 % and must have hand railings. Landings cannot exceed 2% in either direction and need to be at the same elevation as the Finished floor. Thresholds can't exceed 1/2".
11/17/2025 ENGR Engineering Final Partial Pass Okay for level 3 TCO for use as a sales model.