Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-0825-00458

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/20/2026 RSBU - Building Final  Re-inspection required 1/20/26: hvac condenser Disconnect box requires 3' clearance in front, accessible route does not meet requirements, properly secure conduit at wall will appropriate fasteners,
KO at main panel must be sealed, thermostat shall be no higher than 48" above finish floor, no attic access, no garage access, domestic water has not been hooked up, sewer connection has not been made, expansion tank required at water heater due to a closed loop system. Stopped inspection more items may be added. Please call future inspections under commercial permit for sales office and model home (this permit is directly correlated with the SFR)
11/17/2025 RSBU - Building Final  Partial Pass Okay for level 3 TCO for use as a sales model.