Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0825-00458
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 9/30/25: fasteners at shear walls shall penetrate no more than 1/8", fasteners at shear wall 11 shall be spaced at 4" at edge and 12" at field, Anchor bolts at shear wall 11 are required at 23" o.c, anchor bolt spacing at exterior walls is 72" o.c (span greater than 72" on north wall), anchor bolts shall be placed no closer than 7X the bolt diameter from edge of sill plate, 2x6 Ledge at back patio must be fastened with 4 16d nails at 16" o.c, 2x6 rafters at back patio must be spaced at 16" o.c,RSP4 spacing should be 32" o.c (missed on south wall, improperly installed MASA clip at north wall midway, 7 fasteners minimum at masa clip to suffice for 1/2" anchor bolts, shot pins must be spaced at 36" o.c at interior non-load bearing walls. Roof sheathing at garage must be properly fastened, anchor bolts must be in middle third of plate. | |
| 10/03/2025 | COT - RSBU - Roof Nailing | Passed |