Permit Details

Status:
Issued
Type:
Commercial Building
Address:
3520 S KINO PW
Address NEW:
3520 S KINO PW
Apply Date:
11/19/2024
Applicant:
David Openshaw
Description:
New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure

Permit Reviews

Permit Number - TC-COM-1124-02231
Permit Status: Issued
Permit Description: New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure
Start Date Submittal Complete Date Status  
11/22/2024 COMMERCIAL REVIEW - FULL v.1 12/17/2024 REQUIRES RESUBMIT Review Details
05/23/2025 RESTAMP - COMMERCIAL v.1 05/29/2025 APPROVED Review Details
01/31/2025 COMMERCIAL REVIEW - FULL v.2 02/18/2025 REQUIRES RESUBMIT Review Details
08/04/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 08/06/2025 APPROVED Review Details
04/16/2025 RESTAMP - COMMERCIAL v.1 04/23/2025 APPROVED Review Details
03/26/2025 COMMERCIAL REVIEW - FULL v.3 04/16/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1124-02231
Permit Status: Issued
Permit Description: New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure
Total Outstanding Activity Conditions - 1
Date Name
12/16/2025 WATER STERILIZATION REPORT IS REQUIRED.

Conditions

Permit Number - TC-COM-1124-02231
Permit Status: Issued
Permit Description: New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure
Date Description Comments
11/22/2024 Please contact Pima County Addressing to resolve issue. Addressing@pima.gov or 520-724-9512
11/22/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
04/30/2025 Prior to Issuance: This project requires issuance of a Development Package (DP) permit prior to issuance of this permit. Prior to TCO/Final: This project requires full completion of a Development Package (DP) permit prior to Temporary C of O and/or final completion this permit.
11/22/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
11/22/2024 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-1124-02231
Permite Description: New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure
Total Outstanding Inspections - 12
Last Inspection Date Description Inspector Results Comments
12/17/2025 COT - HCBU - TCO N/A Not Ready
08/13/2025 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass Canopy column footings as per RFI #17 at GL: 1/A - E.5; 6 footings. Ok to place concrete in progress areas.
11/13/2025 COT - HCEL - Electrical Above Ceiling N/A Partial Pass 11-13-25: okay to install ceiling tiles at dining and restroom vestibule areas.
11/07/2025 COT - LCME - Mechanical Final N/A Partial Pass Hood duct system wrapped.
07/30/2025 COT - HCPL - Rough Soil N/A Partial Pass 7-30-25: grease interceptor verified per plans & under test-okay to backfill progress areas.
10/15/2025 COT - HCPL - Plumbing Progress N/A Partial Pass 10-15-25: main water line stemmed into utility room room verified under test at 60 psi. Okay to backfill progress areas.
09/15/2025 COT - HCPL - Plumbing Intermediate N/A Partial Pass Kitchen area: fryer area and walk-in cooler areas. Ok to,cover progress areas.
01/09/2026 COT - HCPL - Plumbing Final N/A Re-inspection required Inspector Findings – 01/09/2026
Exterior receptacles do not have required approved weatherproof covers.
Junction box covers are missing at the fire riser.
Air gap is required at the fire riser.
ADA receptacle requirements are not met.
Circuit B-82 has no power.
Water heater manufacturer’s required side clearance is not met.
All disconnect boxes are not labeled.
Roof receptacle has no power.
All rooftop equipment must be labeled, and proper amperage must be verified for all equipment.
Insulation at the ice maker is not properly protected.
Kitchen equipment is not properly secured to the wall.
Circuit B-27 is off at the seating area.
NOTE: on the panels that were penetrated via screws, one of the following options is required.1) a UL inspection by the manufacturer is required and the inspection report would have to submitted to the for city for review 2) a letter by the UL manufacturer documenting the panels are safe to use and there is no possibility of arching 3) replace panels.
Conditions for Occupancy:
Engineering final inspection must be approved prior to issuance of Certificate of Occupancy (CofO).
Water sterilization is required prior to issuance of Temporary Certificate of Occupancy (TCO) above Level 1.
Pima County Health Department inspection must be approved prior to issuance of TCO above Level 2.
10/15/2025 COT - HCPL - Gas Pressure Test N/A Partial Pass 10-15-25: verified gas pressure test at 15psi on approximately 120' of exterior piping from the southeast quad of site which runs west to a future canopy.
Note: interior gas lines have not been installed and are required to be tested.
09/02/2025 COT - HCEL - Outdoor Lighting N/A Partial Pass 9-2-25: reinforcement on 13 light pole cages verified per plans. Okay for concrete placement at progress areas.
01/09/2026 COT - HCEL - Electrical Final N/A Re-inspection required Inspector Findings – 01/09/2026
Exterior receptacles do not have required approved weatherproof covers.
Junction box covers are missing at the fire riser.
Air gap is required at the fire riser.
ADA receptacle requirements are not met.
Circuit B-82 has no power.
Water heater manufacturer’s required side clearance is not met.
All disconnect boxes are not labeled.
Roof receptacle has no power.
All rooftop equipment must be labeled, and proper amperage must be verified for all equipment.
Insulation at the ice maker is not properly protected.
Kitchen equipment is not properly secured to the wall.
Circuit B-27 is off at the seating area.
NOTE: on the panels that were penetrated via screws, one of the following options is required.1) a UL inspection by the manufacturer is required and the inspection report would have to submitted to the for city for review 2) a letter by the UL manufacturer documenting the panels are safe to use and there is no possibility of arching 3) replace panels.
Conditions for Occupancy:
Engineering final inspection must be approved prior to issuance of Certificate of Occupancy (CofO).
Water sterilization is required prior to issuance of Temporary Certificate of Occupancy (TCO) above Level 1.
Pima County Health Department inspection must be approved prior to issuance of TCO above Level 2.
09/09/2025 COT - LCBU - Building Final N/A Partial Pass 9-9-25: extended pararpet on high walls (north, south, east & west side) verified per detail S601/A3. Okay to install 5/8" wood deck at progress areas-call for a nailing inspection when ready.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-1124-02231
Permit Description: New construction of a 5,196 sf commercial restaurant with a double-wide drive-thru, 2 Canopies covering drive-thru meal delivery and order point, and a separate trash enclosure
Total Completed Inspections - 27
Date Description Inspector Results Comments
07/01/2025 PDSD Building Division Pre-Construction Meeting Passed
07/24/2025 COT - HCPL - Sewer Passed 7/24/25: Sewer tie in approved. Pending grease interceptor.
10/13/2025 COT - LCME - Kitchen Hood Passed Four kitchen hoods smoke tested: Ok to double fire wrap.
11/14/2025 COT - HCEL - Electrical Intermediate Passed Switch gear cabinet in place. Ok to energize system.
11/26/2025 BULD - Electrical Clearance Passed ECO TEP CLEARANCE
12/17/2025 COT - HCBU - Excavation/Rebar/Zoning Passed
12/17/2025 COT - BULD - SWG Clearance Passed
12/17/2025 COT - HCEL - Electrical Above Ceiling Passed
12/17/2025 COT - HCEL - Electrical Progress Passed
12/17/2025 COT - HCEL - Electrical Underground Passed
12/17/2025 COT - HCPL - Backwater Valve Passed
12/18/2025 TRSP - ROW - Final/Close-Out Passed
01/07/2026 COT - HCPL - Gas Final Passed Gas service complete.
01/07/2026 COT - LCME - Mechanical Final Passed
01/07/2026 COT - FCON - Alarm - Final Passed
01/07/2026 COT - LCEL - Electrical Final Passed
01/07/2026 COT - FCON - Sprinkler - Final Passed
01/07/2026 COT - LCPL - Plumbing Final Passed
01/08/2026 COT - FCON - Fire - Final Passed
01/09/2026 COT - HCEL - Grounding/Bonding Passed
01/09/2026 COT - HCPL - Rough Soil Passed
01/09/2026 COT - HCPL - Plumbing Progress Passed
01/09/2026 COT - HCPL - Plumbing Intermediate Passed
01/09/2026 COT - HCPL - Plumbing Above Ceiling Passed
01/09/2026 COT - HCPL - Yard Water Line Passed
01/09/2026 COT - HCPL - Gas Pressure Test Passed
01/09/2026 COT - HCEL - Outdoor Lighting Passed

Documents

File Name Document Type  
REDBUILT DEFERRED SUBMITTAL 144928 AFP_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-05676 TUCSON MARKETPLACE - KINO PKWY FSU_V1.PDF DOCUMENTS VIEW
05676 TUCSON MARKETPLACE - KINO PARKWAY FSU-RED GEOTECH FINAL REPORT_CONVERT_V1.PDF DOCUMENTS VIEW
CONS-FULL PLAN SET_V3.PDF DOCUMENTS VIEW
STRUCTURAL CALCS_V1.PDF DOCUMENTS VIEW
TC-COM-1124-02231 - CHICK-FIL-A 05676 TUCSON MKT KINO PKWY - SIGNED_V1.PDF DOCUMENTS VIEW