Permit Details

Status:
Issued
Type:
Commercial Building
Apply Date:
09/19/2023
Applicant:
Jay Hanson
Description:
Medical Office Tenant improvement

Permit Reviews

Permit Number - TC-COM-0923-02223
Permit Status: Issued
Permit Description: Medical Office Tenant improvement
Start Date Submittal Complete Date Status  
03/16/2024 COMMERCIAL REVIEW - FULL v.4 03/19/2024 APPROVED Review Details
11/03/2023 COMMERCIAL REVIEW - FULL v.4 11/07/2023 APPROVED Review Details
01/29/2024 COMMERCIAL REVIEW - FULL v.1 01/29/2024 REQUIRES RESUBMIT Review Details
10/30/2023 COMMERCIAL REVIEW - FULL v.3 10/31/2023 REQUIRES RESUBMIT Review Details
11/07/2023 RESTAMP - COMMERCIAL v.1 11/07/2023 APPROVED Review Details
02/09/2024 COMMERCIAL REVIEW - FULL v.3 03/06/2024 REQUIRES RESUBMIT Review Details
09/19/2023 COMMERCIAL REVIEW - FULL v.1 10/18/2023 REQUIRES RESUBMIT Review Details
10/20/2023 COMMERCIAL REVIEW - FULL v.2 10/24/2023 REQUIRES RESUBMIT Review Details
02/01/2024 COMMERCIAL REVIEW - FULL v.2 02/01/2024 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-COM-0923-02223
Permit Status: Issued
Permit Description: Medical Office Tenant improvement
Date Description Comments
09/19/2023 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0923-02223
Permite Description: Medical Office Tenant improvement
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
12/07/2023 COT - HCPL - Plumbing Intermediate N/A Re-inspection required 12/7/23: vents are dry, fill to the roof.
12/07/2023 COT - HCBU - Framing N/A Re-inspection required 12/7/23: OSB shear back of over-notched plumbing wall at south area. Seal gap between top plate and wall at all furred out walls.
04/15/2024 BULD - Electrical Clearance N/A Not Applicable
04/15/2024 COT - BULD - SWG Clearance N/A Not Applicable

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0923-02223
Permit Description: Medical Office Tenant improvement
Total Completed Inspections - 19
Date Description Inspector Results Comments
11/30/2023 COT - HCPL - Rough Soil Passed
12/07/2023 COT - HCME - Mechanical Intermediate Passed
12/07/2023 COT - HCEL - Electrical Intermediate Passed
12/08/2023 COT - HCPL - Plumbing Intermediate Passed 12/8/23: Vent stack is under a water test without any leaks. Okay to proceed with roof insulation.
12/08/2023 COT - HCBU - Framing Passed 12-8-23: Plumbing wall in south area has OSB Plywood attached to strengthen the over-notched studs. Spray foam has been applied between furred out walls and block walls. Okay to proceed with installation of insulation and drywall.
12/11/2023 COT - HCPL - Plumbing Above Ceiling Passed Roof drains are installed and under water test with no leaks. Okay to proceed.
04/15/2024 COT - FCON - Fire - Final Passed
04/15/2024 ENGR Engineering Final Passed
04/15/2024 TRSP - ROW - Final/Close-Out Passed
04/15/2024 COT - HCBU - Preslab Passed
04/16/2024 COT - HCBU - Building Above Ceiling Passed
04/16/2024 COT - HCEL - Electrical Above Ceiling Passed
04/16/2024 COT - HCME - Mechanical Above Ceiling Passed
04/16/2024 COT - HCME - Mechanical Final Passed
04/22/2024 COT - HCPL - Gas Pressure Test Passed Gas line is under air pressure with no leaks. Okay to connect to meter.
04/22/2024 COT - BULD - SWG Clearance Passed Gas line is under air pressure with no leaks. Okay to connect to meter. SWG CLEARANCE ISSUED FOR SWG to connect meter.
04/22/2024 COT - HCBU - Building Final Passed GFCI has been installed in janitors room and at counter next to sink. Mirror and sink have been lowered to meet ADA requirements. Construction, mechanical, electrical, and plumbing are complete and functional. Okay to issue a Certificate of Completion or Certificate of Occupancy for this project and permit.
04/22/2024 COT - HCEL - Electrical Final Passed GFCI has been installed in janitors room and at counter next to sink. Mirror and sink have been lowered to meet ADA requirements. Construction, mechanical, electrical, and plumbing are complete and functional. Okay to issue a Certificate of Completion or Certificate of Occupancy for this project and permit.
04/22/2024 COT - HCPL - Plumbing Final Passed GFCI has been installed in janitors room and at counter next to sink. Mirror and sink have been lowered to meet ADA requirements. Construction, mechanical, electrical, and plumbing are complete and functional. Okay to issue a Certificate of Completion or Certificate of Occupancy for this project and permit.

Documents

File Name Document Type  
5_CONSTRUCTION_SET_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
4_CONSTRUCTION_SET_V2.PDF DOCUMENTS VIEW