Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0923-02223
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/06/2024 | Site Engineering | NOT REQUIRED | |||
| 03/04/2024 | Site Zoning | NOT REQUIRED | |||
| 03/06/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/12/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural N/A Building N/A Mechanical N/A Electrical N/A Plumbing(P) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 2/12/2024 9:15:56 AM 1) General: The original set of plans show an electric water heater which is now being revised to a gas water heater. The small utility room needs to show the source of combustion air, make-up air for the exhaust fan in the utility room, and electrical drawings and calculation revisions. Please submit the revised set of drawings and details for all affected sheets. (2018 IBC section 107, 2018 IFGC section 304, 2018 IMC section 403, 2017 NEC Article 220) |
||
| 02/09/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |