Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Issued
Type:
Commercial Building
Apply Date:
06/20/2024
Applicant:
Jose contreras
Description:
Tenant Improvement for La Michoacana

Permit Reviews

Permit Number - TC-COM-0624-01182
Permit Status: Issued
Permit Description: Tenant Improvement for La Michoacana
Start Date Submittal Complete Date Status  
06/21/2024 COMMERCIAL REVIEW - LIMITED v.1 07/09/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0624-01182
Permit Status: Issued
Permit Description: Tenant Improvement for La Michoacana
Total Outstanding Activity Conditions - 4
Date Name
07/08/2024 AIR BALANCING REPORT IS REQUIRED.
07/08/2024 COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED.
07/08/2024 Separate submittal to PC Industrial Wastewater Control is required for new interceptors and separators. Contact Lucinda.Hyatt@pima.gov for review and assessment of the proposed grease interceptor.
07/08/2024 WATER STERILIZATION REPORT IS REQUIRED.

Conditions

Permit Number - TC-COM-0624-01182
Permit Status: Issued
Permit Description: Tenant Improvement for La Michoacana
Date Description Comments
07/09/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
07/08/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0624-01182
Permite Description: Tenant Improvement for La Michoacana
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
09/04/2024 COT - LCBU - Framing N/A Re-inspection required 8/8/24: diagonal bracing required at new bathroom framing, pony wall not installed at time of inspection, damaged studs must be replaced at existing bathroom.
9/4/24: no access to site.
09/05/2024 BULD - Electrical Clearance N/A Not Applicable
09/05/2024 COT - BULD - SWG Clearance N/A Not Applicable
09/05/2024 COT - LCME - Mechanical Above Ceiling N/A Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.
08/08/2024 COT - LCEL - Electrical Intermediate N/A Re-inspection required 7/8/24: missing receptacles throughout in wall,
09/05/2024 COT - LCEL - Electrical Above Ceiling N/A Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.
09/05/2024 COT - LCPL - Plumbing Above Ceiling N/A Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.
09/05/2024 COT - LCME - Mechanical Intermediate N/A Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0624-01182
Permit Description: Tenant Improvement for La Michoacana
Total Completed Inspections - 5
Date Description Inspector Results Comments
07/29/2024 COT - LCBU - Preslab Passed 7/29/24: Preslab passed ok to proceed
08/08/2024 COT - LCPL - Plumbing Intermediate Passed
09/05/2024 COT - LCBU - Framing Passed
09/05/2024 COT - LCPL - Rough Soil Passed 7/26/24: plumbing underground per plans. Partial pass pending grease interceptor.
9/5/24: Grease interceptor installed and under test ok to backfill. Shading required.
09/05/2024 COT - LCEL - Electrical Intermediate Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
24118 SYSTEMS DESIGN REPORT_V1.PDF DOCUMENTS VIEW
CONS-1_A-1 THRU E4.0 1656 W VALENCIA LA MICHOACANA 06-19-24_V1.PDF DOCUMENTS VIEW