Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Above Ceiling
Permit Number - TC-COM-0624-01182
Inspection Description - COT - LCME - Mechanical Above Ceiling
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2024 | COT - LCME - Mechanical Above Ceiling | Re-inspection required | 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection. |