Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Intermediate
Permit Number - TC-COM-0624-01182
Inspection Description - COT - LCME - Mechanical Intermediate
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2024 | COT - LCME - Mechanical Intermediate | Re-inspection required | 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection. |