Inspection Status: Re-inspection required

Inspection History: COT - LCPL - Plumbing Above Ceiling

Permit Number - TC-COM-0624-01182

Inspection Description - COT - LCPL - Plumbing Above Ceiling

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/05/2024 COT - LCPL - Plumbing Above Ceiling Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.