Inspection Status: Re-inspection required
Inspection History: COT - LCEL - Electrical Above Ceiling
Permit Number - TC-COM-0624-01182
Inspection Description - COT - LCEL - Electrical Above Ceiling
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2024 | COT - LCEL - Electrical Above Ceiling | Re-inspection required | 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection. |