Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Above Ceiling 

Permit Number - TC-COM-0624-01182

Inspection Description - COT - LCEL - Electrical Above Ceiling 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/05/2024 COT - LCEL - Electrical Above Ceiling  Re-inspection required 9/5/24: seismic wire required at all registers and light fixtures, seismic wire required every 4' o.c at grid ceiling, properly support flex duct, properly support MC cable off of Grid. Please provide ladder for inspection.