Permit Details

Status:
Issued
Type:
Commercial Building
Address:
7655 S KOLB RD
Address NEW:
7655 S KOLB RD
Apply Date:
05/10/2024
Applicant:
Colton Lloyd
Description:
New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department

Permit Reviews

Permit Number - TC-COM-0524-00906
Permit Status: Issued
Permit Description: New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department
Start Date Submittal Complete Date Status  
10/21/2024 COMMERCIAL REVIEW - LIMITED v.4 11/14/2024 APPROVED Review Details
05/14/2024 COMMERCIAL REVIEW - LIMITED v.1 06/04/2024 REQUIRES RESUBMIT Review Details
09/16/2024 COMMERCIAL REVIEW - LIMITED v.3 10/01/2024 REQUIRES RESUBMIT Review Details
11/14/2024 RESTAMP - COMMERCIAL v.1 11/15/2024 APPROVED Review Details
06/24/2024 COMMERCIAL REVIEW - LIMITED v.2 07/15/2024 REQUIRES RESUBMIT Review Details
05/01/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 05/06/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0524-00906
Permit Status: Issued
Permit Description: New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department
Total Outstanding Activity Conditions - 9
Date Name
05/09/2025 Submission of the final Elevation Certificate and completion of the Floodplain Use Permit is required PRIOR TO FINALING this permit.
06/03/2024 This project requires the completion of a Fire Construction Permit PRIOR TO FINALING this permit.
06/04/2024 Masonry Inspection Report submittal review is required.
06/04/2024 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.
06/04/2024 Post-Installed Anchor Inspection Report is required.
06/04/2024 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
06/04/2024 SPECIAL INSPECTION FOR SPECIAL MOMENT RESISTING STEEL FRAMES IS REQUIRED.
06/04/2024 SPECIAL INSPECTION FOR WELDING IS REQUIRED.
07/12/2024 Deferred submittal for Fabric Shade Canopy. Should this option be executed, Provide Fabric Shade Canopy drawings to include steel frame, steel columns, footing & shade. Provide the Shade Flame Spread Rating Index as well as the Fire Propagation Performance information as well as the Structural Drawings and Calculations prior to Building Final Inspection.

Conditions

Permit Number - TC-COM-0524-00906
Permit Status: Issued
Permit Description: New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department
Date Description Comments
05/09/2025 An intermediate Elevation Certificate is required PRIOR TO GRADING and/or PRE-SLAB INSPECTION.
05/14/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
06/04/2024 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0524-00906
Permite Description: New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department
Total Outstanding Inspections - 13
Last Inspection Date Description Inspector Results Comments
05/01/2025 COT - LCPL - Sewer N/A Partial Pass 5/1/25: progress inspection for rough plumbing in room 104, ok to backfill.
05/12/2025 COT - LCPL - Yard Water Line N/A Partial Pass 5/7/25: 10' stretch of 2" copper for water line under pressure. Stubbing under exterior wall. Ok to proceed.
5/12/25: 120' of 2" soft copper type K per plans. Per approved plans. Proper burial depth and tracer wire installed. Ok to proceed with backfill at progress location.
05/14/2025 LCBU - Preslab and Floodplain Inspection N/A Partial Pass 5-14-25, verified that vapor in place together with reinforcement per plans. Per contractor, a civil engineer verified elevation to one-hundredth of an inch. However, their 3rd party (Meridian) will inspect after pour and complete the rest of the required paperwork. Okay to pour at own risk pending floodplain certification.
Note: submit 3rd party and floodplain reports as soon as possible as it's required prior to building final.
06/25/2025 COT - LCPL - Rough Soil N/A Partial Pass Domestic water and DWV on test 114,106,107,108,109,103. 6/25/2025
06/27/2025 COT - LCEL - Electrical Progress N/A Partial Pass All in wall electrical in place. Okay to proceed progress areas. 6/27/2025
08/04/2025 COT - LCEL - Electrical Intermediate N/A Partial Pass
08/06/2025 COT - LCEL - Electrical Underground N/A Partial Pass X2 1” Two light poles connected to ground box. Daisy chained to flag pole. 2” future solar to ground box also 1 1/4”future Ev charger. Okay to backfill progress areas. Shading required. 8/6/2025
07/14/2025 COT - LCEL - Electrical Above Ceiling N/A Partial Pass 7-14-25: above ceiling mep's in room's 114, 107 & 103 verified per plans-lans. Okay to close hard lid areas.
06/03/2025 COT - LCBU - Masonry Pregrout N/A Partial Pass 6-3-25: cmu wall at Gridline B top out at 22' approved.
12/19/2025 BULD - Electrical Clearance N/A Not Applicable
12/19/2025 COT - BULD - SWG Clearance N/A Not Applicable
12/19/2025 COT - FCON - Fire - Final N/A Partial Pass Key switch for gate still needs to be tested and a key for the Knox Box is still needed.
12/19/2025 COT - LCBU - Building Final N/A Re-inspection required 12/19/25: conducted a general walk through of the entire building, receptacle at roof for HVAC servicing not energized, receptacle in ada bathroom south east corner not energized, all disconnect boxes must be labeled, vertical grab bars at ADA shower required, all exterior plastic piping must be coated for UV protection, utilities closet not ready (booster pump must be installed) properly support all piping vertically and horizontally in utility room, all ceiling tiles must be installed, extension bar at roof access required on ladder, seal all ductwork at RTUs under sun shade for duct flex connector, properly secure conduit at exterior disconnect box, wiring at conduit for gate motor must be installed at time of inspection, site work is incomplete (engineering final not ready), fire final required prior to issuance of building final, R.O.W final required prior to issuance of building final. Please go through all required conditions and ensure they are uploaded to your permit prior to calling in building finals. Backflow preventer must be replaced for correct size. Please call in all inspections on permit card.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0524-00906
Permit Description: New construction of a building and the affiliated site work for the use as an office building for the Tucson Police Department
Total Completed Inspections - 3
Date Description Inspector Results Comments
05/05/2025 COT - LCPL - Plumbing Intermediate Passed 5-5-25, underground plumbing verified as per approved plans. Okay to backfill with shading materials.
06/20/2025 COT - HCBU - Roof Nailing Passed
06/25/2025 COT - HCPL - Plumbing Intermediate Passed Domestic water and DWV on test 114,106,107,108,109,103. 6/25/2025

Documents

File Name Document Type  
TPD EASTSIDE ANNEX -WOOD I-JOISTS DEFERRED SUBMITTAL (SSE REVIEWED)_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-TPD ANNEX - CONSTRUCTION PLANS_V3_V4.PDF DOCUMENTS VIEW
2_TPD EASTSIDE ANNEX - CLMOR COMMENT LETTER.PDF DOCUMENTS VIEW