Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
In Review
Type:
Commercial Building
Address NEW:
530 E VALENCIA RD
Apply Date:
05/02/2024
Applicant:
Avery Hall
Description:
Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps

Permit Reviews

Permit Number - TC-COM-0524-00779
Permit Status: In review
Permit Description: Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps
Start Date Submittal Complete Date Status  
05/08/2024 COMMERCIAL REVIEW - FULL v.1 06/10/2024 REQUIRES RESUBMIT Review Details
12/16/2024 COMMERCIAL REVIEW - FULL v.3 01/10/2025 REQUIRES RESUBMIT Review Details
06/17/2025 RESTAMP - COMMERCIAL v.1 06/18/2025 APPROVED Review Details
06/10/2026 COMMERCIAL REVIEW - FULL v.1 N/A IN REVIEW Review Details
06/10/2025 COMMERCIAL REVIEW - FULL v.6 06/17/2025 APPROVED Review Details
01/14/2025 COMMERCIAL REVIEW - FULL v.4 02/05/2025 REQUIRES RESUBMIT Review Details
12/14/2024 COMMERCIAL REVIEW - FULL v.2 12/14/2024 REQUIRES RESUBMIT Review Details
02/10/2025 COMMERCIAL REVIEW - FULL v.5 02/26/2025 REQUIRES RESUBMIT Review Details
12/10/2025 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/18/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0524-00779
Permit Status: In review
Permit Description: Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps
Total Outstanding Activity Conditions - 9
Date Name
02/14/2025 Applies to All: Deferred submittal documents must be submitted and approved prior to installation of construction elements included in deferred submittal documents.
02/14/2025 Special inspections must be performed by an approved third party inspection agency at the owner's expense. Special inspection forms and reports are required to be submitted for review and approved prior to issuance of final approval documents.
02/14/2025 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
02/14/2025 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
02/14/2025 Masonry Inspection Report submittal review is required.
02/14/2025 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.
02/14/2025 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
12/11/2025 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
12/11/2025 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.

Conditions

Permit Number - TC-COM-0524-00779
Permit Status: In review
Permit Description: Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps
Date Description Comments
05/08/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
12/14/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
02/14/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
02/14/2025 STATE FIRE MARSHAL INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION

Outstanding Inspections

Permit Status: In Review
Permit Number: TC-COM-0524-00779
Permite Description: Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
03/18/2026 COT - HCBU - Stem Wall/Retaining Wall N/A Not Ready Inspection was for trash enclosure. Referred to site team. 3/18/2026
04/21/2026 COT - HCBU - Excavation/Rebar/Zoning N/A Re-inspection required 4-21-26: per NEC, Table 300.5 minimal trench depth (cover) for a 1" Schedule 40 electrical conduit is 18" in residential, commercial, or industrial applications from top of conduit to finished grade. Reschedule this inspection when ready. Okay for concrete placement at light pole cage east of the trash enclosure.
04/24/2026 COT - HCEL - Grounding/Bonding N/A Partial Pass 4-24-26: verified bonding at canopy.
05/07/2026 COT - HCEL - Electrical Underground N/A Partial Pass 5-7-26: 1" schedule 40 electrical conduits for light poles approved. Okay to backfill approximately 500' of open trench using shading materials.
04/30/2026 COT - HCBU - Preslab N/A Partial Pass 4-30-26: reinforcement for fuel tank mat with #4's @12" o.c. approved. Okay for concrete placement.
04/15/2026 COT - HCEL - Outdoor Lighting N/A Partial Pass 4-15-26: approximately 300' of main water line verified under test. Line stems from the air/water located on north side and runs south where there are 2 hose bibs and continues southeast side of building. Okay to backfill progress areas using shading materials.
06/08/2026 COT - HCEL - Electrical Intermediate N/A Partial Pass 6-8-26: pending Load calcs required for new circuit tied to incorrect panels -revision required.
06/05/2026 COT - HCBU - Building Final N/A Re-inspection required 6/5/26: all EMT explosion proof fittings shall be opened to verify Chico sealant, Load calcs required for new circuit tied to incorrect panels (revision required), panel schedule must be corrected and legible, all finals shall be called in, conditions must be satisfied, state fire marshal approval required prior to final.

Completed Inspections

Permit Status: In Review
Permit Number: TC-COM-0524-00779
Permit Description: Rev.1: 06/10/2026 New high speed diesel canopy with 3 pumps with existing convenience store and fuel canopy with 10 pumps
Total Completed Inspections - 11
Date Description Inspector Results Comments
06/05/2026 COT - FCON - Fire - Final Passed
06/08/2026 COT - HCBU - Stem Wall/Retaining Wall Passed
06/08/2026 COT - HCBU - Excavation/Rebar/Zoning Passed
06/08/2026 COT - HCBU - Framing Passed
06/08/2026 COT - HCEL - Grounding/Bonding Passed
06/08/2026 COT - HCEL - Electrical Underground Passed
06/08/2026 COT - HCBU - Preslab Passed
06/08/2026 TRSP - ROW - Final/Close-Out Passed
06/11/2026 COT - HCEL - Electrical Intermediate Passed 6-11-26: electrical intermediates approved.
06/11/2026 COT - HCEL - Electrical Final Passed 6-11-26: electrical final approved.
06/11/2026 ENGR Engineering Final Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
SPECIAL INSPECTIONS CERTIFICATE (SIGNED)-2025-12-09_V1.PDF DOCUMENTS VIEW
CONS-CK (2703386) E VALENCIA RD - NOGALES HWY, TUCSON AZ 202402-024_COMBINED R3_V6.PDF DOCUMENTS VIEW