Permit: TC-COM-0524-00779

Parcel: 13816001G


Addresses:

530 E VALENCIA RD

Inspection Status: Partial Pass

Inspection History: COT - HCEL - Electrical Underground 

Date Description Inspector Results Comments
03/12/2026 COT - HCEL - Electrical Underground  Partial Pass 3-12-26: verified trench depth at over 2' containing 15 plus- 3/4" & 1" secondary electrical conduits. Conduits stem from the southeast corner of site and run approximately 90' in a northwest direction. Okay to backfill progress areas.
COT - HCEL - Electrical Underground  Partial Pass 4-6-26: verified 15 schedule 40 electrical conduits consisting of 5-1" & 10-3/4" secondary conduits that extend from a south direction and run northwest to canopy. Okay to backfill approximately 50' of open trench using shading materials.
04/21/2026 COT - HCEL - Electrical Underground  Re-inspection required 4-21-26: light pole conduit inspection -per NEC, Table 300.5 minimal trench depth (cover) for a 1" Schedule 40 electrical conduit is 18" in residential, commercial, or industrial applications from top of conduit to finished grade. Reschedule this inspection when ready. Okay for concrete placement at light pole cage east of the trash enclosure.
05/07/2026 COT - HCEL - Electrical Underground  Partial Pass 5-7-26: 1" schedule 40 electrical conduits for light poles approved. Okay to backfill approximately 500' of open trench using shading materials.
06/08/2026 COT - HCEL - Electrical Underground  Passed