Inspection Status: Re-inspection required
Inspection History: COT - HCBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2026 |
COT - HCBU - Building Final |
|
Re-inspection required |
6/5/26: all EMT explosion proof fittings shall be opened to verify Chico sealant, Load calcs required for new circuit tied to incorrect panels (revision required), panel schedule must be corrected and legible, all finals shall be called in, conditions must be satisfied, state fire marshal approval required prior to final. |
| 06/11/2026 |
COT - HCBU - Building Final |
|
Partial Pass |
6-11-26: pending fire & engineering approval together with Load calc revision for new circuit tied to incorrect panel, pending conditions together with 3rd party outdoor lighting report & city approval. |