Permit: T22CM04532
Permit Details
Status:
Issued
Type:
Residential Building - One or Two Family
Address:
3020 E 17TH ST
Address NEW:
3020 E 17TH ST
Apply Date:
06/17/2022
Applicant:
EDUARDO SABORI
Description:
R-Master Bedroom & Garage Addition
Permit Reviews
Permit Number - T22CM04532
Permit Status: Issued
Permit Description: R-Master Bedroom & Garage Addition
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/17/2022 | RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO | 07/05/2022 | COMPLETED |
| 04/04/2023 | RESIDENTIAL NEW DWELLING v.3 | 04/07/2023 | APPROVED |
| 12/12/2022 | RESIDENTIAL NEW DWELLING v.1 | 01/13/2023 | REQUIRES RESUBMIT |
| 04/07/2023 | RESTAMP - RESIDENTIAL v.1 | 04/10/2023 | APPROVED |
| 03/03/2023 | RESIDENTIAL NEW DWELLING v.2 | 03/23/2023 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - T22CM04532
Permit Status: Issued
Permit Description: R-Master Bedroom & Garage Addition
Total Outstanding Activity Conditions - 2
| Date | Name |
|---|---|
| 03/23/2023 | Manual J must be submitted and approved prior to Mechanical Final.. |
| 03/23/2023 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Conditions
Permit Number - T22CM04532
Permit Status: Issued
Permit Description: R-Master Bedroom & Garage Addition
| Date | Description | Comments |
|---|---|---|
| 04/07/2023 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/integrated-planning/PDSD/PDSD_Owner_Builder_Affidavit.pdf, is required prior to issuance of permit. |
Outstanding Inspections
Permit Status: Issued
Permit Number: T22CM04532
Permite Description: R-Master Bedroom & Garage Addition
Total Outstanding Inspections - 14
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2023 | COT - RSBU - Excavation/Rebar/Zoning | N/A | Re-inspection required | 5-12-23: 1-Setbacks are not according to approved plans. 2-Footings are not 12" below undisturbed soil. 3-Sleeve piping in footings. 4- Install Hold downs per plans. |
| 05/12/2023 | COT - RSBU - Preslab | N/A | Re-inspection required | 5-12-23: 1-Setbacks are not according to approved plans. 2-Footings are not 12" below undisturbed soil. 3-Sleeve piping in footings. 4- Install Hold downs per plans. |
| 05/12/2023 | COT - RSPL - Yard Water Line | N/A | Re-inspection required | 5-12-23: Tied into existing lateral. 1-Need tracer wire on exterior piping. |
| 05/12/2023 | COT - RSPL - Sewer | N/A | Partial Pass | 5-12-23: Tied into existing lateral. 1-Need tracer wire on exterior piping; ok inside footprint. |
| 06/21/2023 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | N/A | Re-inspection required | |
| 02/07/2024 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
| 02/07/2024 | BULD - Electrical Clearance | N/A | Not Applicable | |
| 06/21/2023 | COT - RSBU - Interior Shear Bracing | N/A | Not Ready | |
| 02/07/2024 | COT - RSEL - Electrical Underground | N/A | Not Applicable | |
| 02/07/2024 | COT - RSEL - Grounding/Bonding | N/A | Not Applicable | |
| 02/07/2024 | COT - RSEL - Outdoor Lighting | N/A | Re-inspection required | 2/7/24: exterior receptacles must be WR, Arc-fault breaker's missing at panel (multiple locations missing), sediment trap at water heater missing, sediment trap at A/C unit not properly installed, pipes on exterior must be coated for UV protection, water lines at water heater must be properly insulated and wrapped for if protection, hose bibs must have vacuum breaker, handrails at stair way not per code, drain at bathroom lavatory must be smooth interior, receptacle on south west corner of garage not on same GFCI circuit as garage receptacles. Properly secure A/C whip and thermostat whip, AC is being over Amped (max 25). |
| 02/07/2024 | RSBU - Building Final | N/A | Re-inspection required | 2/7/24: exterior receptacles must be WR, Arc-fault breaker's missing at panel (multiple locations missing), sediment trap at water heater missing, sediment trap at A/C unit not properly installed, pipes on exterior must be coated for UV protection, water lines at water heater must be properly insulated and wrapped for if protection, hose bibs must have vacuum breaker, handrails at stair way not per code, drain at bathroom lavatory must be smooth interior, receptacle on south west corner of garage not on same GFCI circuit as garage receptacles. Properly secure A/C whip and thermostat whip, AC is being over Amped (max 25). |
| 02/07/2024 | COT - RSPL - Plumbing Final | N/A | Re-inspection required | 2/7/24: exterior receptacles must be WR, Arc-fault breaker's missing at panel (multiple locations missing), sediment trap at water heater missing, sediment trap at A/C unit not properly installed, pipes on exterior must be coated for UV protection, water lines at water heater must be properly insulated and wrapped for if protection, hose bibs must have vacuum breaker, handrails at stair way not per code, drain at bathroom lavatory must be smooth interior, receptacle on south west corner of garage not on same GFCI circuit as garage receptacles. Properly secure A/C whip and thermostat whip, AC is being over Amped (max 25). |
| 02/07/2024 | COT - RSME - Mechanical Final | N/A | Re-inspection required | 2/7/24: exterior receptacles must be WR, Arc-fault breaker's missing at panel (multiple locations missing), sediment trap at water heater missing, sediment trap at A/C unit not properly installed, pipes on exterior must be coated for UV protection, water lines at water heater must be properly insulated and wrapped for if protection, hose bibs must have vacuum breaker, handrails at stair way not per code, drain at bathroom lavatory must be smooth interior, receptacle on south west corner of garage not on same GFCI circuit as garage receptacles. Properly secure A/C whip and thermostat whip, AC is being over Amped (max 25). |
Completed Inspections
Permit Status: Issued
Permit Number: T22CM04532
Permit Description: R-Master Bedroom & Garage Addition
Total Completed Inspections - 13
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2023 | COT - RSPL - Rough Soil | Passed | ||
| 05/17/2023 | COT - RSBU - Excavation/Rebar/Zoning | Passed | Footings have been dug to 12" deep. Sleeves have been installed where sewer line crosses footing. Shear wall hold downs have been installed per plans. Rebar mat needs to be supported with dobies to keep it off of subsoil. | |
| 05/17/2023 | COT - RSBU - Preslab | Passed | Rebar mat is in place, needs dobies to keep it off of subsoil. Compaction is complete. Okay to pour concrete slab. | |
| 05/17/2023 | COT - RSPL - Yard Water Line | Passed | 5-17-23: Tracer wire has been added around sewer pipe and waterline. Sleeves have been added where sewer and water line cross footing. | |
| 05/17/2023 | COT - RSPL - Sewer | Passed | 5-17-23: Tracer wire has been added around sewer pipe. Sleeves have been added where sewer and water line cross footing. | |
| 06/21/2023 | COT - RSBU - Roof Nailing | Passed | ||
| 09/12/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | ||
| 09/12/2023 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | ||
| 02/07/2024 | COT - RSBU - Interior Shear Bracing | Passed | ||
| 03/28/2024 | RSBU - Building Final | Passed | ||
| 03/28/2024 | COT - RSPL - Plumbing Final | Passed | ||
| 03/28/2024 | COT - RSME - Mechanical Final | Passed | ||
| 03/28/2024 | COT - RSEL - Electrical Final | Passed |