Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T22CM04532

Parcel: 129052440


Addresses:

3020 E 17TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
02/07/2024 COT - RSME - Mechanical Final  Re-inspection required 2/7/24: exterior receptacles must be WR, Arc-fault breaker's missing at panel (multiple locations missing), sediment trap at water heater missing, sediment trap at A/C unit not properly installed, pipes on exterior must be coated for UV protection, water lines at water heater must be properly insulated and wrapped for if protection, hose bibs must have vacuum breaker, handrails at stair way not per code, drain at bathroom lavatory must be smooth interior, receptacle on south west corner of garage not on same GFCI circuit as garage receptacles. Properly secure A/C whip and thermostat whip, AC is being over Amped (max 25).
03/28/2024 COT - RSME - Mechanical Final  Passed