Permit Details

Status:
Needs Resubmittal
Type:
Commercial Building
Apply Date:
05/24/2022
Applicant:
Description:
New Retail & Warehouse building

Permit Reviews

Permit Number - T22CM03945
Permit Status: Needs resubmittal
Permit Description: New Retail & Warehouse building
Start Date Submittal Complete Date Status  
05/24/2022 COMMERCIAL - BLDG/FIRE/ZONING/ENG 07/07/2022 COMPLETED Review Details
08/21/2023 COMMERCIAL REVIEW - FULL v.4 08/31/2023 APPROVED Review Details
12/18/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 12/19/2024 REQUIRES RESUBMIT Review Details
08/31/2023 RESTAMP - COMMERCIAL v.1 09/07/2023 APPROVED Review Details
12/23/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.2 12/23/2024 REQUIRES RESUBMIT Review Details
11/07/2022 COMMERCIAL REVIEW - FULL v.1 12/14/2022 REQUIRES RESUBMIT Review Details
04/20/2023 COMMERCIAL REVIEW - FULL v.2 05/16/2023 REQUIRES RESUBMIT Review Details
06/24/2023 COMMERCIAL REVIEW - FULL v.3 07/07/2023 REQUIRES RESUBMIT Review Details
03/11/2024 COMMERCIAL REVIEW - FULL v.1 03/14/2024 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - T22CM03945
Permit Status: Needs resubmittal
Permit Description: New Retail & Warehouse building
Total Outstanding Activity Conditions - 3
Date Name
03/18/2024 Sewer condition must be accepted and released by Pima County prior to issuance of a Temporary Certificate of Occupancy.
05/07/2024 AIR BALANCING REPORT IS REQUIRED.
05/07/2024 COMMISSIONING REPORT IS REQUIRED.

Conditions

Permit Number - T22CM03945
Permit Status: Needs resubmittal
Permit Description: New Retail & Warehouse building
Date Description Comments
05/07/2024 SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
05/07/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
05/07/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
05/07/2024 SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED.
05/07/2024 SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED.
12/18/2024 Masonry Inspection Report submittal review is required.
12/18/2024 SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED.
03/18/2024 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. Contact sewer@pima.gov for review and assessment.
05/07/2024 SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED.
05/07/2024 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.
05/07/2024 WATER STERILIZATION REPORT IS REQUIRED.

Outstanding Inspections

Permit Status: Needs Resubmittal
Permit Number: T22CM03945
Permite Description: New Retail & Warehouse building
Total Outstanding Inspections - 17
Last Inspection Date Description Inspector Results Comments
03/18/2024 COT - HCBU - Excavation/Rebar/Zoning N/A Partial Pass 3/5/24 partial approval or site fence wall southside approximately 500 feet from south east corner, OK to place concrete for footer
3/7/24 next 500' to entry road
3/18/24: north 6' screen wall 500' approved by special inspector.
05/03/2024 COT - HCPL - Plumbing Progress N/A Partial Pass 2/6/24: plumbing underground per plan and under test ok to backfill.
5/3/24: sewer tap passed. Ok to backfill. shading required
02/20/2024 BULD - Electrical Clearance N/A Partial Pass 2/20/24: passed by Ricky on 2/19/24.
2/23/24 TMPP CLEARANCE RESENT TO TEP
08/16/2024 COT - HCBU - Building Above Ceiling N/A Partial Pass Corrections were made for room #110. Okay to proceed progress areas. 8/16/2024
05/30/2024 COT - HCBU - Building Progress N/A Partial Pass 4/12/24: 500' of CMU Stem wall, screen wall on south side of project approved by third party inspector. 0-2' AFF.
4/16/24: 446' of CMU Screen wall south side of project. 0-3' AFF. Approved by third party inspector.
4/17/24: 216' of CMU Screen wall south side of project reinforcement per plan ok to grout and cap. 216' of CMU Stem wall west side of project reinforcement per plan ok to grout.
Partial approval from HCS to approximately 60% of distance to building OK to cover
4/22/24: partial approval from HCS to 75% of distance to building ok to cover.
4/25/24: west site wall 0'-84' south and 0'-108' north of sw opening, 108'-240' North of opening.
4/30/24: Partial approval for underground fiber to 2 1/2 inch conduit from pole box to front of building and 4 inch to from same location to first curb to the west
4/30/24: south side wall east of job entrance 0-4' AFF. CMU wall
5/2/24: north east wall at site entrance 0-4' AFF ok to grout, south east wall at site entrance ok to top out.
5/13/24: no inspection needed.
5/30/24: 2" pvc main from south west corner of building to 180' west of building pending point of connection at backflow preventer. Ok to backfill. Shading required
05/03/2024 COT - HCBU - Roof Nailing N/A Partial Pass 4/24/24: roof nailing on east and west sides of office sheathing fastened per plan ok to proceed.
5/3/24: roof nailing on southside of office sheathing passed. Ok to proceed
12/02/2024 COT - HCEL - Electrical Final N/A Partial Pass 12/2/24: exterior receptacles must be WR GFCI, exhaust fan in office bathroom no power, GFCI required at break room outlets, dishwasher must be properly installed/supported, overflow switch required at air handlers, supports at water heater copper pipes must be coated, Bathroom signage must be installed at time of inspection, condenser unit tripped breaker multiple times during inspection. OK FOR LEVEL 2 TCO.
07/22/2024 COT - HCEL - Electrical Underground N/A Not Ready 7/22/24: not ready
12/02/2024 COT - HCME - Mechanical Final N/A Partial Pass 12/2/24: exterior receptacles must be WR GFCI, exhaust fan in office bathroom no power, GFCI required at break room outlets, dishwasher must be properly installed/supported, overflow switch required at air handlers, supports at water heater copper pipes must be coated, Bathroom signage must be installed at time of inspection, condenser unit tripped breaker multiple times during inspection. OK FOR LEVEL 2 TCO.
05/03/2024 COT - HCME - Mechanical Intermediate N/A Partial Pass 5/3/24: mechanical intermediate passed. Pending drops to registers.
12/02/2024 COT - HCPL - Plumbing Final N/A Partial Pass 12/2/24: exterior receptacles must be WR GFCI, exhaust fan in office bathroom no power, GFCI required at break room outlets, dishwasher must be properly installed/supported, overflow switch required at air handlers, supports at water heater copper pipes must be coated, Bathroom signage must be installed at time of inspection, condenser unit tripped breaker multiple times during inspection. OK FOR LEVEL 2 TCO.
05/01/2024 COT - HCPL - Plumbing Intermediate N/A Partial Pass 5/1/24: plumbing in wall at office area passed. Ok to proceed.
02/06/2024 COT - HCPL - Rough Soil N/A Partial Pass 2/6/24: plumbing underground per plan and under test ok to backfill. Sewer connection pending
11/27/2024 COT - FCON - Fire - Final N/A Partial Pass Approved for TCO level 2. Shall provide Knox gate key switch. Magnetic doors shall be tied into alarm. FDC locking caps and Knoxbox.
06/17/2024 COT - HCEL - Electrical Intermediate N/A Partial Pass 6/17/24: Ufer ground good to go. Partial-pass. Ok to proceed.
12/02/2024 COT - HCBU - Building Final N/A Partial Pass 12/2/24: exterior receptacles must be WR GFCI, exhaust fan in office bathroom no power, GFCI required at break room outlets, dishwasher must be properly installed/supported, overflow switch required at air handlers, supports at water heater copper pipes must be coated, Bathroom signage must be installed at time of inspection, condenser unit tripped breaker multiple times during inspection. OK FOR LEVEL 2 TCO.
ENGR Engineering Final N/A Scheduled

Completed Inspections

Permit Status: Needs Resubmittal
Permit Number: T22CM03945
Permit Description: New Retail & Warehouse building
Total Completed Inspections - 29
Date Description Inspector Results Comments
02/16/2024 COT - HCEL - Electrical Progress Passed
02/26/2024 COT - HCBU - Preslab Passed
04/26/2024 COT - HCPL - Sewer Passed Partial approval from HCS to approximately 60% of distance to building OK to cover
4/22/24: partial approval from HCS to 75% of distance to building ok to cover.
4/26/24: Sewer connection complete and under test ok to backfill.
05/09/2024 COT - HCBU - Framing Passed
05/22/2024 COT - HCBU - Firewall/Fire Barrier/Firestop Passed 5/9/24: not ready
5/16/24: fire wall passed on north exterior wall on demising wall between office area and warehouse. Pending north interior wall of office demising wall.
5/22/24: fire wall passed ok to tape and mud.
11/12/2024 BULD - Electrical Clearance Passed 2/20/24: passed by Ricky on 2/19/24.
11/12/24: ECO TEP CLEARANCE AT 4758 E VALENCIA RD.
11/27/2024 COT - FCON - Sprinkler - Final Passed
12/13/2024 COT - HCBU - Building Above Ceiling Passed
12/13/2024 COT - HCBU - Building Progress Passed
12/13/2024 COT - HCBU - Exterior Clips/Sheathing Passed
12/13/2024 COT - HCBU - Interior Shear Bracing Passed
12/13/2024 COT - HCBU - Roof Nailing Passed
12/13/2024 COT - HCEL - Electrical Above Ceiling Passed
12/13/2024 COT - HCEL - Electrical Final Passed
12/13/2024 COT - HCEL - Electrical Underground Passed
12/13/2024 COT - HCEL - Outdoor Lighting Passed
12/13/2024 COT - HCME - Mechanical Above Ceiling Passed
12/13/2024 COT - HCME - Mechanical Final Passed
12/13/2024 COT - HCME - Mechanical Intermediate Passed
12/13/2024 COT - HCME - Mechanical Underground Passed
12/13/2024 COT - HCPL - Backwater Valve Passed
12/13/2024 COT - HCPL - Plumbing Above Ceiling Passed
12/13/2024 COT - HCPL - Plumbing Final Passed
12/13/2024 COT - HCPL - Plumbing Intermediate Passed
12/13/2024 COT - HCPL - Rough Soil Passed
12/13/2024 COT - FCON - Fire - Final Passed
12/13/2024 COT - FCON - Alarm - Final Passed
12/19/2024 COT - HCEL - Electrical Intermediate Passed
12/19/2024 COT - HCME - Mechanical Progress Passed

Scheduled Inspections

Scheduled Inspections - T22CM03945
Status: Needs Resubmittal
Description: New Retail & Warehouse building
Scheduled Date Description Entered By Entered Date
12/24/2024 ENGR Engineering Final Scheduled
For information about today’s scheduled inspections please refer to the PDSD Daily Inspections Dashboards (Desktop) PDSD Daily Inspections Dashboards (Mobile) .

Documents

File Name Document Type  
CHLORINATION MUELLER FULL REPORT-2024-12-13_V1.PDF DOCUMENTS VIEW
3_BLDG PLAN SET_V1.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
3_BLDG PLAN SET_V1.PDF DOCUMENTS VIEW