Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - HCME - Mechanical Final
Permit Number - T22CM03945
Inspection Description - COT - HCME - Mechanical Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2024 | COT - HCME - Mechanical Final | Partial Pass | 12/2/24: exterior receptacles must be WR GFCI, exhaust fan in office bathroom no power, GFCI required at break room outlets, dishwasher must be properly installed/supported, overflow switch required at air handlers, supports at water heater copper pipes must be coated, Bathroom signage must be installed at time of inspection, condenser unit tripped breaker multiple times during inspection. OK FOR LEVEL 2 TCO. | |
12/13/2024 | COT - HCME - Mechanical Final | Passed |