Permit: T09CM01288
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
3945 E PARADISE FALLS DR #201
Address NEW:
3945 E PARADISE FALLS DR #201
Apply Date:
05/21/2009
Applicant:
N/A
Description:
TI: OFFICE
Contractors:
- A F STERLING HOME BUILDERS LTD
Permit Reviews
Permit Number - T09CM01288
Permit Status: C of o
Permit Description: TI: OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/21/2009 | PLANS OK TO SUBMIT - COMM | 05/21/2009 | COMPLETED |
| 05/21/2009 | 3RD PARTY REVIEW-COMMERCIAL | 06/24/2009 | COMPLETED |
| 06/24/2009 | POST 3RD PARTY REVIEW | 06/29/2009 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T09CM01288
Permit Status: C of o
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/21/2009 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T09CM01288
Permit Description: TI: OFFICE
Total Completed Inspections - 22
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2009 | FRAMING | JBURGE | Approved | IVRS - Inspection :* 1) OK TO SHEETROCK PENDING ELECTRIC AND PLUMBING INTERMEDIATES |
| 10/15/2009 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | IVRS - Inspection :* |
| 10/16/2009 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) PROVIDE BACKING AROUND ALL CEILING BOXES-WILL CHECK ON NEXT INSPECTION 2) OK TO SHEETROCK HARD LIDS ONLY 3) NEED TO SEE CONDENSATE PIPING IN WALLS 4) SUSPENDED ROUGH DUCT PROVIDE CONICAL OR HIGH EFFICIENCY TAPS AS PER PLANS 5) NEED TO SEE INSIDE ROOF CURBS FOR INSULATION REQUIRED ON PLANS |
| 11/12/2009 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* 1) OK TO TAPE AND TEXTURE THROUGHOUT 2) LETTER FROM ENGINEER DATED 11/08/09 EFFECTING REPAIR OF CMU PILASTER AT LINE D-3; ON JOB SITE (MICHAEL E. HARRIS ENGINEER OF RECORD) |
| 12/30/2009 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
| 12/30/2009 | ELECTRIC - ABOVE CEILING | RMORENO | Approved | IVRS - Inspection :* 1. NEED TO COVER J-BOXES & STRAP MC 1' FROM BOX 2. NEED TO PUT PLASTIC BUSHING FOR LOW VOLTAGE EMT 3. NEED TO SEE LITE INSTALLED 4. NEED EXTION RINGS FOR J-BOX & KO SEALS 5. ROOM 32, 31, 18, 19, 26, 25, 23, 4, 24, 22, 21, 29, 20, 10, 16, 11, 12, 13, 14 |
| 12/30/2009 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* 1) NEED STAMPED LETTER FOR CHANGE TO ABS ABOVE FLOOR AS NOTED 10/15 2) NEED TO SEE CLOSET FLANGES 3) OK TO INSTALL CEILING TILES AFGTER REPLACING INSULATION SHIELD |
| 12/30/2009 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* |
| 12/31/2009 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
| 01/12/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR #L1,L2,L3 & L4 PER R. MORENO |
| 01/21/2010 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 01/21/2010 | FIRE - FINAL | LTHOMAS | Approved | |
| 01/22/2010 | NPPO - FINAL | JLIVILLE | Approved | N/A |
| 01/22/2010 | LANDSCAPE - FINAL | JLIVILLE | Approved | N/A |
| 01/22/2010 | SIGN - FINAL | JYBARRA | Approved | |
| 01/22/2010 | ENGINEERING - FINAL | DROBERTS | Approved | |
| 01/25/2010 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* 1) LIGHTING, POWER, EXITS AND EM LIGHT ALL OK |
| 01/25/2010 | RIGHT OF WAY - FINAL | PWhiddon | Approved | |
| 01/29/2010 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 01/29/2010 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* 1) ALL TRADES AND FIRE FINALS ARE COMPLETE |
| 01/29/2010 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) PLUMBING FINAL OK |
| 02/01/2010 | PERMIT FINALED | JWEATHER | Approved |