Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2010 | MECHANICAL - INTERMEDIATE | Approved | ||
| 10/16/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE BACKING AROUND ALL CEILING BOXES-WILL CHECK ON NEXT INSPECTION 2) OK TO SHEETROCK HARD LIDS ONLY 3) NEED TO SEE CONDENSATE PIPING IN WALLS 4) SUSPENDED ROUGH DUCT PROVIDE CONICAL OR HIGH EFFICIENCY TAPS AS PER PLANS 5) NEED TO SEE INSIDE ROOF CURBS FOR INSULATION REQUIRED ON PLANS |