Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/25/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ID UNITS OR DISCONNECTS WITH THE PROPER SUITE NUMBERS 2) PROVIDE TEST ON DUCT SMOKE DETECTOR 3) RELOCATE SEWER VENT MINIMUM 10' AWAY FROM FRESH AIR INTAKE HP-2 4) PROVIDE AIR BLAANCE REPORT 5) LETTER OK FROM ENGINEER TO ALLOW STRAIGHT START COLLARS |