Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
01/08/2010 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
12/31/2009 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/30/2009 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/31/2009 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/21/2009 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/15/2009 PLUMBING - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) C1 SPECIFIED, PROVIDE LETTER FOR CHANGE OF PLANS SPECS. RED LINE CHANGES
2) PROVIDE TEST ON DWV, 100 PSI ON DOMESTIC WATER
3) OK TO INSULATE HOT WATER-NOTE 1" REQUIRED ON CIRCULATING SYSTMES PER IECC
4) C1 CLOSET FLANGES ARE NOT APPROVED
5) NOTE: 3" CLOSET