Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/11/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) ITEMS ON LIST ALL OK
12/30/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. NEED TO COVER J-BOXES & STRAP MC 1' FROM BOX
2. NEED TO PUT PLASTIC BUSHING FOR LOW VOLTAGE EMT
3. NEED TO SEE LITE INSTALLED
4. NEED EXTION RINGS FOR J-BOX & KO SEALS
5. ROOM 32, 31, 18, 19, 26, 25, 23, 4, 24, 22, 21, 29, 20, 10, 16, 11, 12, 13, 14
10/15/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) WALLS IN BLDG ALL OK