Description:
ADDITION:KITCHEN
Architects:
  • BRIGHT, RICK LANE
Contractors:
  • RETRO PRO L L C

Permit Reviews

Permit Number - T08CM01062
Permit Status: C of o
Permit Description: ADDITION:KITCHEN
Start Date Submittal Complete Date Status  
02/24/2009 3RD PARTY REVIEW-REVISION/OTHER-2ND 02/24/2009 COMPLETED Review Details
04/01/2009 3RD PARTY REVIEW-REVISION/OTHER 04/01/2009 COMPLETED Review Details
04/02/2008 PLANS OK TO SUBMIT - 3RD PARTY 04/17/2008 COMPLETED Review Details
04/03/2008 PLANS OK TO SUBMIT - SITE 04/17/2008 COMPLETED Review Details
04/17/2008 3RD PARTY REVIEW-COMMERCIAL 05/23/2008 COMPLETED Review Details
05/23/2008 POST 3RD PARTY REVIEW 09/11/2008 COMPLETED Review Details
05/28/2009 REVISION - - 1ST 05/28/2009 COMPLETED Review Details
10/20/2008 3RD PARTY REVIEW-REVISION/OTHER 02/24/2009 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM01062
Permit Status: C of o
Permit Description: ADDITION:KITCHEN
Total Outstanding Activity Conditions - 1
Date Name
04/02/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T08CM01062
Permit Description: ADDITION:KITCHEN
Total Completed Inspections - 29
Date Description Inspector Results Comments
09/24/2008 PLUMBING - ROUGH, SOIL BBENEDON Approved IVRS - Inspection :*
09/24/2008 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
09/25/2008 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
09/25/2008 BUILDING PRE-SLAB LHANLY Approved IVRS - Inspection :*
10/16/2008 ROOF NAILING JBURGE Approved IVRS - Inspection :*
OK TO DRY IN
10/16/2008 EXT METAL CLIPS/EXT SHEATHING JBURGE Approved IVRS - Inspection :*
ADD ON (DISH AREA) EXTERIOR -- OK TO COVER
11/13/2008 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
MAKE UP AIR DUCTS MUST TERMINATE AT THE HOOD OR PROVIDE HEATED MAKE UP AIR
11/13/2008 STUCCO MESH JBURGE Approved IVRS - Inspection :*
OK TO STUCCO
11/13/2008 FRAMING JBURGE Approved IVRS - Inspection :*
CHANGES SUBMITTED TO PLANS CHECK -- 3RD PARTY
11/19/2008 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
WELDS ON GREASE DUCT ARE OK
OK FOR 1ST LAYER OF FIRE WRAP
11/19/2008 PLUMBING - GAS PRESSURE TEST BBENEDON Approved IVRS - Inspection :*
1. PROVIDE A TEST ON DWV
2. PROVIDE AN APPROVED DOUBLE FIXTURE FITTING
PER UPC 704 AT LAVS
3. SUPPORT AND PROTECT ABS PASSING THRU METAL STUDS
4. SUPPORT AND ISOLATE ALL COPPER
5. HOT WATER PIPING NOT PER PLAN
6. PROVIDE CLEARANCE AROUND HW AND HWR PIPING FOR 1" INSULATION. WIPE CLEAN ALL FLUX. SEE INSTALLATION STANDARDS IS #3
7. CHECK YOUR LAYOUT AT VENTS FOR 3-COMP SINK
8. NOTE: BOILER IS MISSING AN EXPANSION TANK
11/19/2008 ELECTRIC - INTERMEDIATE RMORENO Approved IVRS - Inspection :*
OK WALLS
LINED GROUND SCREWS IN BOXES
11/19/2008 PLUMBING - INTERMEDIATE BBENEDON Approved IVRS - Inspection :
See detailed listing on site.| 999*
03/24/2009 PLUMBING - ABOVE CEILING BBENEDON Approved IVRS - Inspection :*
03/31/2009 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
OK TO TAPE THROUGHOUT
05/18/2009 MECHANICAL - HOOD SYSTEMS JMILITEL Approved IVRS - Inspection :*
PROVIDE THE PROPER REDUCER ON BOILER VENT
VENTS ON CONDENSATE TRAPS TO BE DOWNSTREAM OF TRAP
PROVIDE FILTERS IN FRESH AIR INTAKES
MARK UNIT DATA PLATES AND FUSE ACCORDINGLY
PROVIDE A SUNSHIELD OVER CANVAS CONNECTOR
06/02/2009 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. MORENO
06/05/2009 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
AIR BALANCE OK
06/05/2009 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
06/05/2009 ELECTRIC - FINAL RMORENO Approved IVRS - Inspection :*
ALL ITEMS ON LIST OK
06/05/2009 ELECTRIC - ABOVE CEILING RMORENO Approved
06/05/2009 PLUMBING - FINAL BBENEDON Approved IVRS - Inspection :*
06/05/2009 PLUMBING - GAS PRESS TEST FNL BBENEDON Approved IVRS - Inspection :*
06/05/2009 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
06/09/2009 FIRE - KITCHEN EXH HOOD FINAL CSCHULTZ Approved
06/09/2009 FIRE - FINAL CSCHULTZ Approved
06/09/2009 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
04/07/2010 PERMIT FINALED BGRANT Approved
04/07/2010 HEALTH DEPT - FINAL 724-7908 BGRANT Approved PER DOCUMENTS IN SIRE

Documents

File Name Document Type  
001__G0.0.TIF CONSTRPLANS VIEW
002__S1.0.TIF CONSTRPLANS VIEW
003__S2.1.TIF CONSTRPLANS VIEW
004__S2.2.TIF CONSTRPLANS VIEW
005__A1.1.TIF CONSTRPLANS VIEW
006__A1.1D.TIF CONSTRPLANS VIEW
007__A1.2.TIF CONSTRPLANS VIEW
008__A1.3.TIF CONSTRPLANS VIEW
009__A2.2.TIF CONSTRPLANS VIEW
010__A5.1.TIF CONSTRPLANS VIEW
011__A6.1.TIF CONSTRPLANS VIEW
012__P1.1.TIF CONSTRPLANS VIEW
013__P2.1.TIF CONSTRPLANS VIEW
014__P3.1.TIF CONSTRPLANS VIEW
015__M1.1.TIF CONSTRPLANS VIEW
016__M2.1.TIF CONSTRPLANS VIEW
017__M3.1.TIF CONSTRPLANS VIEW
018__MP1.1.TIF CONSTRPLANS VIEW
019__E1.0.TIF CONSTRPLANS VIEW
020__E2.0.TIF CONSTRPLANS VIEW
021__E3.0.TIF CONSTRPLANS VIEW
022__E4.0.TIF CONSTRPLANS VIEW
023__FS1.TIF CONSTRPLANS VIEW
024__FS5.TIF CONSTRPLANS VIEW
001_S2.3.TIF CONSTRPLANS VIEW
FOODSERVICEEQUIP.TIF DOCUMENTS VIEW
STRUCCALCS.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW
PC HEALTH.PDF DOCUMENTS VIEW
C OF O T08CM01062.PDF DOCUMENTS VIEW