Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM01062

Parcel: 12106220A


Addresses:

5549 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/05/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
06/01/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PROVIDE CORRECT WATER CONN. TO SOAP DISPENSER AT MS
A VACUUM BREAKER MAY NOT HAVE VALVES DNSTREAM
SECURE STOVE SO THAT NO STRAIN IS PLACED ON FLEX
STERILIZATION AND BACKFLOW CERTS ARE ALL OK
05/28/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
05/22/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
C O IN WALL OK TO COVER
05/21/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) DISPOSER CONNECTION IS OK
2) INSTALL CLEANOUT FOR HAND SINKS
3) NEED TO SEE PLAN REVISION FOR FINAL
4) REPLACE DAMAGED CLEANOUT PLUGS WITH PLUGS MADE AND LISTED TO RECEIEVE A SCREW
5) SEAL THREADS
6) 1" AG ABOVE FLOOD LEVEL REQUIRED FOR INDIRECT WASTE
7) NOTE: WATER SYSTEM STERILIZATION IS REQUIRED
8) CONNECT CW TO EXISTING UP STREAM OF CHECK VALVE/SUPPLY TO BOILER
05/18/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. GAS TEST OK
2. MAKE FINAL CONN.
3. INSTALL SEDIMENT TRAP AND RESTRAINT
4. PROVIDE MIXING VALVE AND EXP. TANK AT EXISTING BOILER
5. PROVIDE TYPE L COPPER FOR COOLER SUPPLY
6. SUPPORT. TEST.
7. PLUG AND INSTALL GRATE ON UNUSED FS
8. ONLY ONE SLIP NUT ALLOWED DNSTRM OF P-TRAP
9. PROVIDE PROPER MAKE UP ON SOLVENT WELD FITTINGS
10. PROVIDE PROPER DRAINAGE FITTING ON VENT TAKE OFF
11. PROVIDE A DIRECT CONNECTION FOR DISPOSER
12. PROVIDE ACCESS TO RELIEF VALVE ON BOOSTER. CORRECT DRIP.
13. PROVIDE ACCESS TO 0075 (ROTATE) INSTALL
UNION P-TRAP REQUIRED ON INDIRECT WASTE OVER 5'
14. SUPPORT AND CORRECT SLOPE
15. HAND SINK AT BEV COUNTER (FRONT) REQUIRES A
DIRECT DRAIN CONNECTION AND A PLAN REVISION FOR
WATER & WASTE
16. HB VAC BREAKER