Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* ALL ITEMS ON LIST OK |
|
| 06/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED TO MAKE GFI WORK ON WALK OFF NEED TO BOND SERVICE LUG NEED TO SEE PANEL SCHEDULES |
|
| 06/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED LOCK NUT AND P-BUSHINGS 2) NEED LISTED CONNECTOR FOR LIQUID TIGHT ON ROOF 3) NEED TO BOND SERVICE LUG |
|
| 05/28/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/18/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL BACK FOR REINSPECTION |