Permit: T08CM01062

Parcel: 12106220A


Addresses:

5549 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/28/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/27/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/23/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/23/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PIPE INSULATION AND CLAMPS OK TO COVER
RECALL 03035 FOR CLOSET FLANGE INSP. AFTR. FINISH FLOOR
03/19/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TESTING COMPLETE INSULATION NOT YET COMPLETE - RECALL

CLETE @ 480-567-6395
03/18/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CORRECT CLEANOUT AT K-10 AND M CU
CORRECT SWEEP 3-COMP SINK
BELOW FLOOR CHANGE OK
2" GAS DROP IN WALL OK
03/17/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
03/09/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEW FIXTURE NOT INSTALLED PER PLAN AND
VIOLATES UPC 908.2 BECAUSE OF T 7-5 NOTE #2
2. WATER PIPE SIZING OK STILL NEED TO PROVIDE A CLEARANCE FOR PIPE - INSULATION SPECIFIED
11/19/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/13/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
POST CORRECT ADDRESS AT REAR DOOR
1. SECURE/SUPPORT PIPING T3-2
2. INSTALL BACKING FIXTURE CARRIERS SPECIFIED
3. PROVIDE TEST
4. SWEEPS REQUIRED ON HORIZ. TRAP ARMS
5. DRAINAGE FITTING REQUIRED ON GT VENT
6. TAKE OFF AT 45 DEG's
7. NO PLASTIC EXPOSED TO SUNLIGHT
8. PROVIDE LISTING FOR INSTALLATION OF ANSUL VALVE
ABV ROOF
9. PROVIDE 2 1/2" TEE PER PLAN
10. PROVIDE VENTS FOR FLOW CONTROL AND P-TRAP
AT 3-COMP SINK. SEE ILLUSTRATION AND CODE SEC. 1014.2.1
11. WATER NOT YET COMPLETE. PROVIDE CLEARANCE FOR PIPE INSULATION. REAM ALL COPPER JOINTS AND REMOVE EXCESS FLUX. LIST MAY NOT BE COMPLETE.