Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address NEW:
9460 E GOLF LINKS RD
Apply Date:
06/29/2007
Applicant:
SHAWN MC DONALD
Description:
TI:GROCERY STORE TO INCLUDE SCOPE OF WORK FOR T04EL01975
Architects:
  • JOHN MCDONALD
Contractors:
  • HAUGEBAK CONSTRUCTION COMPANY ,

Permit Reviews

Permit Number - T07CM02800
Permit Status: Expired
Permit Description: TI:GROCERY STORE TO INCLUDE SCOPE OF WORK FOR T04EL01975
Start Date Submittal Complete Date Status  
01/16/2009 3RD PARTY REVIEW-REVISION/OTHER 01/27/2009 COMPLETED Review Details
06/29/2007 3RD PARTY REVIEW-COMMERCIAL TI 07/14/2007 COMPLETED Review Details
07/14/2007 POST 3RD PARTY REVIEW 09/09/2007 COMPLETED Review Details
09/05/2007 3RD PARTY REVIEW-REVISION/OTHER 09/09/2007 COMPLETED Review Details
09/09/2007 POST 3RD PARTY REVIEW 10/05/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM02800
Permit Status: Expired
Permit Description: TI:GROCERY STORE TO INCLUDE SCOPE OF WORK FOR T04EL01975
Total Outstanding Activity Conditions - 1
Date Name
06/29/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07CM02800
Permite Description: TI:GROCERY STORE TO INCLUDE SCOPE OF WORK FOR T04EL01975
Total Outstanding Inspections - 11
Last Inspection Date Description Inspector Results Comments
ELECTRIC - OUTDOOR LIGHTING N/A Not Inspected
02/19/2009 OUTDOOR LIGHTING FINAL N/A Partial Approval IVRS - Inspection :*
05/15/2009 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED -- NEED ELECTRICAL FINAL
12/03/2007 ELECTRIC - ABOVE CEILING N/A Partial Approval IVRS - Inspection :*
OK LIGHTS FOR ISLES 2, 3, 4, 5, 6, 7
12/04/2007 BUILDING ABOVE CEILING N/A Partial Approval IVRS - Inspection :*
BAKERY CEILING GRID ONLY
12/07/2007 BUILDING - PROGRESS N/A Not ready for Inspection IVRS - Inspection :*
12/07/2007 ELECTRIC - PROGRESS N/A Not ready for Inspection IVRS - Inspection :*
12/19/2007 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*
OK FINAL @ BAKERY
12/28/2007 FRAMING N/A Partial Approval IVRS - Inspection :*
EMPLOYEE LOUNGE
12/28/2007 SHEET ROCK NAILING N/A Partial Approval IVRS - Inspection :*
EMPLOYEE LUNCH ROOM SALES AREA SIDE - ONLY
12/28/2007 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
1. OK WALLS BREAKROOM & MEAT DEPT
2. OK HARD LIDS BREAKROOM

Completed Inspections

Permit Status: Expired
Permit Number: T07CM02800
Permit Description: TI:GROCERY STORE TO INCLUDE SCOPE OF WORK FOR T04EL01975
Total Completed Inspections - 17
Date Description Inspector Results Comments
11/28/2007 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
CHECKED WELDS ON DELI GREASE DUCT OK TO FIRE WRAP
CHECKED NEW RETURN AIR DUCT
OK CEILING TILES PRODUCE AREA
12/03/2007 PLUMBING - ABOVE CEILING RRICH Approved IVRS - Inspection :*
CONTRACTOR CANCELLED
12/07/2007 PLUMBING - PROGRESS RRICH Approved IVRS - Inspection :*
(2) 3" VENT THRU ROOF WATER TEST IN STARBUCKS AREA OK
12/14/2007 PLUMBING - PRE SLAB RRICH Approved IVRS - Inspection :*
WATER TEST TO 10' DWV UNDERGROUND EMPLOYEE LOUNGE & (2) FLOOR SINKS FOR LUNCH MEAT CASES, WATER FOR EMPLOYEE SINK OK

1. SHALL SEE WEST FLOOR SINK VENT THRU ROOF TEST AT LATER DATE.
12/14/2007 PLUMBING - GAS PRESSURE TEST RRICH Approved IVRS - Inspection :*
12/19/2007 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
BA-146 & BA-1266 SINKS OK AT BAKERY
REMOVE DWV IN WALL AT STORAGE IN WALL OR CAP PROPERLY (SOUTH WALL)
A REFEE HAS BEEN ADDED TO THIS PERMIT FOR FAILURE TO CONTROL UNSANITARY CONDITION
12/19/2007 PLUMBING - ROUGH, SOIL RRICH Approved WATER TEST UNDERGROUND & FOR FS-1 AND HAND SINK TO EXISTING VENT OK
SHALL SEE CONNECTION TO VENT FOR BOTH FIXTURES
WATER TO HAND SINK MEAT PREP OK
12/19/2007 PLUMBING - ROUGH, SOIL RRICH Approved IVRS - Inspection :*
WATER TEST 2" GREASE WASTE FOR 3-COMP SINK PER REDLINE ON SITE TO EXISTING GREASE TRAP. WATER TEST 2" SANITARY DRAIN FOR FS-1 PER REDLINE ON SITE FOR SANITIZE BOWL 3-COMP SINK. WATER THIS AREA MEAT DEPT. DWV TEST THRU RE-VENT. REDLINES TO BE REVISED AND CITY APPROVED.
12/31/2007 PLUMBING - INTERMEDIATE RLEDONNE Approved IVRS - Inspection :*
HAND SINK IN MEAT PREP DEMO OK ALL PIPING CAPPED IN WALL OK
02/11/2008 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
INSPECTION ON SMALL FRYER HOOD
OK TO USE HOOD
06/26/2008 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
01/28/2009 MECHANICAL - HOOD SYSTEMS JMILITEL Approved IVRS - Inspection :*
01/28/2009 NPPO - FINAL ACONNOR Approved N/A
01/28/2009 LANDSCAPE - FINAL ACONNOR Approved N/A
01/28/2009 FIRE - FINAL LTHOMAS Approved
02/02/2009 RIGHT OF WAY - FINAL MCASTRO Approved PER EMAIL
02/19/2009 MECHANICAL - INTERMEDIATE JMILITEL Approved