Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02800
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OK OUTSIDE WALL @ DELI 2. OK WALL @ NEW WATER HEATER 3. OK RTU FOR BREAK ROOM 4. ELECTRIC ROOM TO BE CLEANED UP. - ELECTRIC ROOM IN HAZARDOUS SITUATION. - NEED TO CLOSE PANELS - INSTALL COVERS WHEN CONSTRUCTION DONE FOR DAY - HAVE ROOM CLEANED UP BEFORE NEXT INSPECTION TO AVOID REFEE |
|
01/14/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BROKEN METAL FLEX @ DAIRY PROMO CASES 2. MISSING COVERS ON JUNCTION BOXES @ DAIRY PROMO CASES 3. BOXES NOT GROUNDED @ DAIRY PROMO CASES 4. RACEWAYS TO BE CONNECTED TO JUNCTION POINTS 5. HAVE OPEN WIRING UNDER DAIRY CASES 6. RECALL WHEN READY 7. INSTALL ALL COVERS @ DAIRY PROMO CASES |
|
12/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS BREAKROOM & MEAT DEPT 2. OK HARD LIDS BREAKROOM |
|
11/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL ACCESSIBLE DISCONNECT FOR PANEL TO STARBUCKS PANEL 2) CHECK BOX FILL FOR TRUCK LIGHTS 3) INSTALL CONNECTOR ON MAKE UP TO TRUCK LIGHTS 4) OK ISLE 13, 12 AND 11 ROW LIGHTING |
|
11/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FEEDER TO PANEL LP 2. 90 DEG. FLEX CONNECTORS NEED TO BE ACCESSIBLE (FLORAL DEPT) 3. OK WIRING IN 30 KVA & 45 KVA XFMRS |
|
11/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 3/4" PVC IN SLAB CEREAL ISLE 2. OK BAKERY PREP WALL |
|
11/05/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY BRIAN |
|
10/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ATTACH BOTTOM END OF WIRES WHEN GRID DONE 2. FINISH VDV AS DISCUSSED 3. EXTRA CONDUCTORS IN RACEWAYS ARE FOR WHAT? 4. OPEN WALL BEHIND SODA MACHINE |
|
10/12/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PVC UNDERGROUND IN FLORAL SALES & PRODUCE AREA 2. CONTACT WILDAN TO ADD 02010 TO ACTIVITY RECEIVED MONEY ORDER #5707924878 FOR $150 FOR AFTER HRS. INSP. |