Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02800
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING @ DELI COOKING AREA |
|
02/01/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
12/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK LIGHTS FOR ISLES 2, 3, 4, 5, 6, 7 |
|
11/28/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK LIGHTS FOR ISLES 10, 9, 8 2. FINAL CEILING APPROVAL WILL BE GIVEN WHEN ALL JUNCTIONS BOXES HAVE BLANKS. ALL MISSING K.O'S ARE SEALED AND OVER FILLED BOXES CORRECTED. |
|
11/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/08/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK PERIMETER CEILING IN PRODUCE DEPT 2. OK FLOOR BOXES END OF ISLE #9 3. NEED PROPER SIZE GROUNDING & WATER BOND TO 45 KVA XFMR 4. DISCONNECTS FOR PANEL TO BE READILY ACCESSIBLE NEC 404.8 |
|
11/06/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/29/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/16/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK 3 3/4" TO COLUMN AT FRONT OF STORE TO FEED NEW PRODUCE UNDERGROUND 2. OK 1 1/4" EMT FROM NEW XFMR TO NEW PANEL AT FRONT OF STORE 3. ENSURE TELEPHONE/DATA CABLES ARE UP OFF OF GRID & SUPPORTED EVERY 6' |