Permit: T07CM02800

Parcel: 13613001S

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02800

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
05/15/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EM LIGHTING TO BE PER PLANS
2. RECALL WHEN READY
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MAU ON ROOF HAD LISTING LABEL INSTALLED IN FIELD AFTER COMPONENTS REPLACED FOR SUPPLY VOLTAGE. ETL INVESTIGATING
2. MISSING EM LIGHTS CANNOT LOCATE LIGHTING FIXTURE SCHEDULE. HAVE ELECTRICAL CONTRACTOR GO THROUGH PLANS AND LIGHTING AND VERIFY EM LIGHTS
01/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STILL NEED TO CHECK EM LIGHTS
2. ROOF INSPECTION
- PROPERLY MOUNT BOXES & DISCONNECTS
- HAVE OPEN WIRING TO EXHAUST FAN INSTALL IN RACEWAYS
- ROOFTOP RECEPT. TO BE GFI PROTECTED
- MAU APPEARS TO BE OVERFUSED
3. NAME PLATE LABEL & LISTING LABEL FOR MAU APPEARS TO BE INSTALLED OVER ANOTHER LABEL AND BOTTOM OF LABEL HAS BEEN REMOVED.
06/26/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
03/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO FINISH MAKE UP AIR FOR EXHAUST HOOD
2. HAVE APPROVED PLANS ON SITE
3. INSTALL MISSING K.O IN BOXES
4. INSTALL MISSING BLANKS ON BOXES
5. LABEL DISCONNECTS FOR LOAD SERVED
6. INSTALL DISCONNECT FOR CONDENSING UNIT
FOR ICE MAKER
7. NEED TO CHECK EM LIGHTS
03/18/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
02/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
DELI
1. STILL NEED PROPER SIZE FUSES FOR PAN WASHER
02/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DELI INSPECTION
1. INSTALL PLATES ON RECEPTACLES
2. SECURE JUNCTION BOXES
3. SECURE MC AND FLEX WITHIN 12" OF BOXES
4. CANNOT USE TECH SCREW FOR CONNECTION OF GROUNDS
5. MARK DISCONNECTS FOR LOAD SERVED
6. MARK NEUTRAL CONDUCTOR
7. CLOSE OPEN JUNCTION BOXES
8. SEAL OPEN KNOCKOUTS
9. REMOVE TAPE @ CONNECTOR TO MC CABLE
10. INSTALL PROPER SIZE FUSES FOR DISHWASHER AND PAN WASHER
02/11/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EVAPORATIVE COOLER FOR DELI HOOD NOT INSTALLED
2. DELI CEILING NOT READY FOR INSPECTION
12/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL @ BAKERY
12/18/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HANDY BOX OVERFILLED @ BAKERY
2. EXCEEDING BEND RADIUS ON MC CABLE IN DISPLAY CASES
3. JUNCTION BOXES TO BE BONDED WITH #12
4. HAVE 30 AMP RECEPTACLES WITH #12 GAUGE WIRE
5. BAKERY AREA NOT READY HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE BAKERY AREA.
6. NEED BARRIER BETWEEN SWITCHES WHEN OVER 300V BETWEEN SWITCHES
12/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONTRACTOR NOT ON SITE. CALLED AHEAD LEFT MESSAGE ON VOICEMAIL
2. RECALL WHEN READY
11/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. IS ELECTRIC ROOM UNDER LOCK & KEY WITH LOCK OUT TAG OUT PROCEDURES IN PLACE? EQUIPMENT BEING LEFT OPEN BOTH 480 & 120 VOLT
2. NEED PANEL DIRECTORY AS PER 408.4

OK STARBUCKS SUBJECT TO ABOVE
11/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FLOOR BOX @ DELI FOR FEEDER TO RELOCATED PANEL
2. OK FINAL FOR KIOSK FLORAL DEPT
10/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK 3/4 PVC TO BAKERY 2 DOOR FREEZER TO REFRIGERATED ISLAND IN FLOOR
- OK OVERHEAD HOME RUNS IN STOCKROOM