Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02800
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EM LIGHTING TO BE PER PLANS 2. RECALL WHEN READY |
|
02/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAU ON ROOF HAD LISTING LABEL INSTALLED IN FIELD AFTER COMPONENTS REPLACED FOR SUPPLY VOLTAGE. ETL INVESTIGATING 2. MISSING EM LIGHTS CANNOT LOCATE LIGHTING FIXTURE SCHEDULE. HAVE ELECTRICAL CONTRACTOR GO THROUGH PLANS AND LIGHTING AND VERIFY EM LIGHTS |
|
01/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. STILL NEED TO CHECK EM LIGHTS 2. ROOF INSPECTION - PROPERLY MOUNT BOXES & DISCONNECTS - HAVE OPEN WIRING TO EXHAUST FAN INSTALL IN RACEWAYS - ROOFTOP RECEPT. TO BE GFI PROTECTED - MAU APPEARS TO BE OVERFUSED 3. NAME PLATE LABEL & LISTING LABEL FOR MAU APPEARS TO BE INSTALLED OVER ANOTHER LABEL AND BOTTOM OF LABEL HAS BEEN REMOVED. |
|
06/26/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
03/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO FINISH MAKE UP AIR FOR EXHAUST HOOD 2. HAVE APPROVED PLANS ON SITE 3. INSTALL MISSING K.O IN BOXES 4. INSTALL MISSING BLANKS ON BOXES 5. LABEL DISCONNECTS FOR LOAD SERVED 6. INSTALL DISCONNECT FOR CONDENSING UNIT FOR ICE MAKER 7. NEED TO CHECK EM LIGHTS |
|
03/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
02/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* DELI 1. STILL NEED PROPER SIZE FUSES FOR PAN WASHER |
|
02/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DELI INSPECTION 1. INSTALL PLATES ON RECEPTACLES 2. SECURE JUNCTION BOXES 3. SECURE MC AND FLEX WITHIN 12" OF BOXES 4. CANNOT USE TECH SCREW FOR CONNECTION OF GROUNDS 5. MARK DISCONNECTS FOR LOAD SERVED 6. MARK NEUTRAL CONDUCTOR 7. CLOSE OPEN JUNCTION BOXES 8. SEAL OPEN KNOCKOUTS 9. REMOVE TAPE @ CONNECTOR TO MC CABLE 10. INSTALL PROPER SIZE FUSES FOR DISHWASHER AND PAN WASHER |
|
02/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EVAPORATIVE COOLER FOR DELI HOOD NOT INSTALLED 2. DELI CEILING NOT READY FOR INSPECTION |
|
12/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL @ BAKERY |
|
12/18/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HANDY BOX OVERFILLED @ BAKERY 2. EXCEEDING BEND RADIUS ON MC CABLE IN DISPLAY CASES 3. JUNCTION BOXES TO BE BONDED WITH #12 4. HAVE 30 AMP RECEPTACLES WITH #12 GAUGE WIRE 5. BAKERY AREA NOT READY HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE BAKERY AREA. 6. NEED BARRIER BETWEEN SWITCHES WHEN OVER 300V BETWEEN SWITCHES |
|
12/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CONTRACTOR NOT ON SITE. CALLED AHEAD LEFT MESSAGE ON VOICEMAIL 2. RECALL WHEN READY |
|
11/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. IS ELECTRIC ROOM UNDER LOCK & KEY WITH LOCK OUT TAG OUT PROCEDURES IN PLACE? EQUIPMENT BEING LEFT OPEN BOTH 480 & 120 VOLT 2. NEED PANEL DIRECTORY AS PER 408.4 OK STARBUCKS SUBJECT TO ABOVE |
|
11/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FLOOR BOX @ DELI FOR FEEDER TO RELOCATED PANEL 2. OK FINAL FOR KIOSK FLORAL DEPT |
|
10/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - OK 3/4 PVC TO BAKERY 2 DOOR FREEZER TO REFRIGERATED ISLAND IN FLOOR - OK OVERHEAD HOME RUNS IN STOCKROOM |