Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL NEW
Apply Date:
03/20/2007
Applicant:
N/A
Description:
NEW HANGER
Architects:
  • STICKLEY DESIGN GROUP
Contractors:
  • GATEWAY EQUITY DEVELOPMENT INC

Permit Reviews

Permit Number - T07CM01130
Permit Status: C of o
Permit Description: NEW HANGER
Start Date Submittal Complete Date Status  
01/28/2009 REVISION - - 1ST 01/28/2009 COMPLETED Review Details
03/20/2007 PLANS OK TO SUBMIT - 3RD PARTY 03/20/2007 COMPLETED Review Details
03/20/2007 3RD PARTY REVIEW-COMMERCIAL 06/23/2007 COMPLETED Review Details
06/23/2007 POST 3RD PARTY REVIEW 06/26/2007 COMPLETED Review Details
06/26/2007 3RD PARTY REVIEW-COMMERCIAL 07/03/2007 COMPLETED Review Details
06/26/2007 OTHER 06/26/2007 COMPLETED Review Details
07/03/2007 POST 3RD PARTY REVIEW 09/12/2007 COMPLETED Review Details
09/27/2007 POST 3RD PARTY REVIEW 10/10/2007 COMPLETED Review Details
10/10/2007 RESUBMITTAL 11/27/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM01130
Permit Status: C of o
Permit Description: NEW HANGER
Total Outstanding Activity Conditions - 1
Date Name
03/20/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T07CM01130
Permit Description: NEW HANGER
Total Completed Inspections - 29
Date Description Inspector Results Comments
04/10/2008 STEM WALL/RETAINING WALL MHENSON Approved IVRS - Inspection :*
04/10/2008 PLUMBING - PRE SLAB RLEDONNE Approved IVRS - Inspection :*
04/10/2008 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection :*
04/11/2008 EXCAVATION/LAYOUT REBAR & ZON MHENSON Approved
04/11/2008 BUILDING PRE-SLAB MHENSON Approved
06/06/2008 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
06/10/2008 BUILDING - FINAL LHANLY Approved PLACEMENT OF BUILDING ON SITE IS IN VIOLATION OF IBC SECTION 412.2.1. "EXTERIOR WALLS LOCATED LESS THAN 30 FET FROM PROPERTY LINES, LOT LINES OR A PUBLIC WAY SHALL HAVE A FIRE RESISTANCE RATING NOT LESS THAN 2 HOURS."

BUILDING OWNER MUST PROVIDE 2 HOUR EXTERIOR WALLS WHERE SAID WALLS ARE LESS THAN 30' FROM LEASED LOT LINE OR A CONTRACTUAL RESTRICTED COVENANT DECLARING A NO-BUILD EASEMENT.
06/27/2008 FRAMING MHENSON Approved IVRS - Inspection :*
ARCHITECT NEEDS TO CONTACT LEE RAY HANLY
REGARDING REVISED PLANS FOR FIRE WALLS AND
PLUMBING DRAIN 412.2.3
07/08/2008 ELECTRIC - TEMP POWER FOR TEST DSANTACR Approved IVRS - Inspection :*
07/09/2008 TEP CLEARANCE - AM BFLORES Approved TEC PER D.SANTA CRUZ
08/01/2008 PLUMBING - YARD WTR LINE/TEST RRICH Approved IVRS - Inspection :*
08/06/2008 PLUMBING - INTERMEDIATE RLEDONNE Approved IVRS - Inspection :*
08/07/2008 EXT METAL CLIPS/EXT SHEATHING MHENSON Approved IVRS - Inspection :*
08/08/2008 PLUMBING - SEWER HCS CONNECT RLEDONNE Approved IVRS - Inspection :*
COMPLETE LIST #1 FROM 8/6/08
08/13/2008 PLUMBING - ABOVE CEILING RLEDONNE Approved IVRS - Inspection :*
10/29/2008 ELECTRIC - ABOVE CEILING DSANTACR Approved IVRS - Inspection :*
1. BEND OUT CLIPS ON FIXTURES
2. MOVE DISC. SW FOR EXH. FAN 2ND FLOOR OFFICE
10/29/2008 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
CLOSET FLANGE OK
10/30/2008 SHEET ROCK NAILING MHENSON Approved IVRS - Inspection :*
ANY PENETRATIONS THRU FIRE WALL NEED FIRE CAULKING
10/30/2008 BUILDING ABOVE CEILING MHENSON Approved IVRS - Inspection :*
11/05/2008 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
OK FOR CEILING TILES
01/23/2009 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
04/03/2009 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
05/08/2009 PLUMBING - ROOF DRAINS RLEDONNE Approved IVRS - Inspection :*
05/08/2009 FIRE - FINAL LTHOMAS Approved
05/11/2009 PLUMBING - ROUGH, SOIL RLEDONNE Approved
06/03/2009 RIGHT OF WAY - FINAL LLOPEZ Approved PER EMAIL
06/03/2009 SIGN - FINAL JYBARRA Approved
06/03/2009 ENGINEERING - FINAL MCARREON Approved
06/30/2009 FIRE - HYDRANTS LTHOMAS Approved PER INSP CARD

Documents

File Name Document Type  
C OF O_06-30-2009.TIF CERT OF OCC VIEW
T07CM01130_001.TIF CONSTRPLANS VIEW
T07CM01130_002.TIF CONSTRPLANS VIEW
T07CM01130_003.TIF CONSTRPLANS VIEW
T07CM01130_004.TIF CONSTRPLANS VIEW
T07CM01130_005.TIF CONSTRPLANS VIEW
T07CM01130_006.TIF CONSTRPLANS VIEW
T07CM01130_007.TIF CONSTRPLANS VIEW
T07CM01130_008.TIF CONSTRPLANS VIEW
T07CM01130_009.TIF CONSTRPLANS VIEW
T07CM01130_010.TIF CONSTRPLANS VIEW
T07CM01130_011.TIF CONSTRPLANS VIEW
T07CM01130_012.TIF CONSTRPLANS VIEW
T07CM01130_013.TIF CONSTRPLANS VIEW
T07CM01130_014.TIF CONSTRPLANS VIEW
T07CM01130_015.TIF CONSTRPLANS VIEW
T07CM01130_016.TIF CONSTRPLANS VIEW
T07CM01130_017.TIF CONSTRPLANS VIEW
T07CM01130_018.TIF CONSTRPLANS VIEW
T07CM01130_019.TIF CONSTRPLANS VIEW
T07CM01130_020.TIF CONSTRPLANS VIEW
T07CM01130_021.TIF CONSTRPLANS VIEW
T07CM01130_022.TIF CONSTRPLANS VIEW
T07CM01130_023.TIF CONSTRPLANS VIEW
T07CM01130_024.TIF CONSTRPLANS VIEW
T07CM01130_025.TIF CONSTRPLANS VIEW
T07CM01130_026.TIF CONSTRPLANS VIEW
T07CM01130_027.TIF CONSTRPLANS VIEW
T07CM01130_028.TIF CONSTRPLANS VIEW
T07CM01130_029.TIF CONSTRPLANS VIEW
T07CM01130_030.TIF CONSTRPLANS VIEW
T07CM01130_031.TIF CONSTRPLANS VIEW
001_M-1.TIF CONSTRPLANS VIEW
002_P-1.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW