Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2007 ROBERT SHERRY WATER REVIEW Denied Tucson Water does not have a ¾" meter available; 5/8", 1", 1.5", 2" are the commonly available meter sizes. Tucson Water limits the use of a 5/8" water meter to a maximum demand of 10 GPM and a 1" water meter to 25 GPM. Revise the proposed meter size appropriately.
06/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/26/2007 MARTIN BROWN FIRE REVIEW Denied The total area of the two hangers, 15,000 sf, exceeds the allowable area for an S1 or S2 without automatic sprinklers. There is not enough distance or a fire wall to have the buildings considered seperate buildings.

The travel distance from second floor exceeds the 75 feet allowed by IFC Table 1018.2
06/26/2007 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/26/2007 SUE REEVES OUT TO CUSTOMER Completed