Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T07CM01130
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2009 | PLUMBING - SEWER HCS CONNECT | Approved | ||
08/08/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* COMPLETE LIST #1 FROM 8/6/08 |
|
08/06/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) PROVIDE RED LINE DRAWINGS FOR COOL AND DRAIN TO BE APPROVED BY CITY OF TUCSON AT LATER DATE 2) PROVIDE SUPPORT ON ALL PIPING 3) REPAIR LEAK ON 2ND FLOOR AND RETEST 4) INSULATE PER KEY NOTES |
|
08/05/2008 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* TEST TO HOLD WITH NO LEAKAGE. PROVIDE THIN WALL PVC BUSHING PRIMED & GLUED ON TO SDR35 WITH APPROVED MISSION STYLE PLASTIC X PLASTIC COUPLING. PROVIDE GREEN TRACER WIRE ON SEWER. |
|
08/01/2008 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* ALL PIPING TO BE SUPPORTED AT CORRECT INTERVALS WITH APPROVED METHODS WITH TEST IN PLACE AT TIME OF INSPECTION |