Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T07CM01130
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
04/03/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HANDRAILS BOTH SIDES OF STAIRS IBC 1009.10 2. ADA TOILET 16 TO 18" OFF FINISH WALL 3. NEED TRADE FINALS AND FIRE C OF O 4. BALLARDS FOR MECH. EQUIP. |
|
06/10/2008 | BUILDING - FINAL | Denied | PLACEMENT OF BUILDING ON SITE IS IN VIOLATION OF IBC SECTION 412.2.1. "EXTERIOR WALLS LOCATED LESS THAN 30 FET FROM PROPERTY LINES, LOT LINES OR A PUBLIC WAY SHALL HAVE A FIRE RESISTANCE RATING NOT LESS THAN 2 HOURS." BUILDING OWNER MUST PROVIDE 2 HOUR EXTERIOR WALLS WHERE SAID WALLS ARE LESS THAN 30' FROM LEASED LOT LINE OR A CONTRACTUAL RESTRICTED COVENANT DECLARING A NO-BUILD EASEMENT. |