Inspection History Details
Permit: T07CM01130
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 10/30/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE BUSHINGS IN FAN COIL KNOCKOUTS 2. PROVIDE OVERFLOW SENSORS IN SECONDARY DRAINS 3. PROVIDE PLUGS IN CONDENSATE PIPING 4. I.D FAN COILS 5. INSTALL FLEX DUCTS EXACTLY PER DETAILS ON PLANS 6. USE ONLY UL 181 FX DUCT TAPE 7. PROVIDE OUTSIDE AIR TO FAN COILS 8. PROVIDE HEAT STRIPS AS PER PLANS 9. PROVIDE FRESH AIR INTAKES AS PER PLANS 10. CONDENSOR & COOLERS MUST HAVE GUARDS. SEE ENGINEER 11. PROVIDE A LIGHT AND RECEPTACLE IN ATTIC |
|
| 08/12/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONDENSATE IN WALLS OK TO COVER MECHANICAL ONLY |
|
| 08/01/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |