Permit: T07CM01130

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM01130

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
10/30/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE BUSHINGS IN FAN COIL KNOCKOUTS
2. PROVIDE OVERFLOW SENSORS IN SECONDARY DRAINS
3. PROVIDE PLUGS IN CONDENSATE PIPING
4. I.D FAN COILS
5. INSTALL FLEX DUCTS EXACTLY PER DETAILS ON PLANS
6. USE ONLY UL 181 FX DUCT TAPE
7. PROVIDE OUTSIDE AIR TO FAN COILS
8. PROVIDE HEAT STRIPS AS PER PLANS
9. PROVIDE FRESH AIR INTAKES AS PER PLANS
10. CONDENSOR & COOLERS MUST HAVE GUARDS.
SEE ENGINEER
11. PROVIDE A LIGHT AND RECEPTACLE IN ATTIC
08/12/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CONDENSATE IN WALLS OK TO COVER MECHANICAL ONLY
08/01/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*